Page 34
See next page for fault codes.
SETTING INSTRUCTIONS (
THERMOSTATS MARKED TLK31)
NOTE : These parameter settings are programmed by the supplier to the figures shown below and
should not need altering.
1. To Program the Set Point. Press down P: SP (Set Point) and current set point value will be displayed alternately.
Press the or key to change the value of SP. Once the desired value is displayed press P to memorise the
value. The display will revert to the present reading.
NOTE : If anything else shows on the display leave alone for 1 minute, until the display returns to normal.
2. To Program the Parameters. Press and hold down the P key for approximately 2 seconds. You will then enter the
Programme Control Menu. Press the key to reach ConF then press P again and enter the Password -281 by
holding the key. If you pass -281 press the key to go back, then press P again, this will take you into the
Programmable Menu. To read or change the setting press P, then to change the setting
(if needed) press the or key . Once the correct setting is reached press P again. To move to the next setting
press the or key and repeat above.
*** Note some functions are not present either because they are instrument dependent or because they are disabled.
To return to Programmable Group Menu leave keys alone for approximately 20 seconds.
To return to Normal Mode leave alone for approximately 20 seconds.
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
THERMOSTAT CONTROL
PARAMETER SETTING INSTRUCTIONS AA300AVH(F) AIR
PARAMETER
FUNCTION
SETTING
NAME
AIR
GROUP
כ
SP (RELATIVE TO SET POINT )
nSP
FACTORY SETTING
1
SP1
SET POINT 1
28.0
SPLL
LOW SET POINT
10.0
SPHL
HIGH SET POINT
40.0
GROUP
כ
InP (RELATIVE TO THE MEASURED OUTPUT )
SEnS
PROBE TYPE
Ptc
SSC
LOW SCALE LIMIT
FSC
HIGH SCALE LIMIT
dp
NO OF DECIMAL FIGURES
1
Unit
TEMP UNITS
º C
FiL
INPUT DIGITAL FILTER
1.0
Fild **
FACTORY SET PASSWORD
OFF
OFSt
MEASURING OFFSET
0.0
rot
ROT OF MEASURING STRAIGHT LINE
1.000
InE
OPE FUNC IN CASE OF ERROR
Our
OPE
OUTPUT PWR IN CASE OF ERROR
0
Dif
DIGITAL INPUTS FUNCTION
noF
GROUP
כ
Out (RELATIVE TO OUTPUTS)
01F
FUNCTIONING OF OP1
ALno
02F
FUNCTIONING OF OP2
1.rEG
03F
FUNCTIONING OF OP3
Alno
04F
FUNCTIONING OF OP4
Alno
GROUP
כ
AL1 (RELATIVE TO ALARM AL1)
0AL1
OUTPUT, ALARM AL1 ADDRESSED
Out1
AL1t
ALARM AL1 TYPE
LodE
Ab1
ALARM AL1 FUNCTIONING
0
AL1
ALARM AL1 THRESHOLD
-4.5
AL1L
LOW THRESHOLD BAND ALARM AL1
-10.0
AL1H
HIGH THRESHOLD BAND ALARM AL1
-1.0
HAL1
ALARM AL1 HYSTERESIS
0.5
AL1d
ACTIVATION DELAY OF ALARM AL1
OFF
AL1i
ALARM AL1 WHEN MEAS ERROR
no
PARAMETER
FUNCTION
SETTING
NAME
AIR
GROUP
כ
AL2 (RELATIVE TO ALARM AL2)
0AL2
OUTPUT, ALARM AL2 ADDRESSED
Out3
AL2t
ALARM AL2 TYPE
HidE
Ab2
ALARM AL2 FUNCTIONING
0
AL2
ALARM AL2 THRESHOLD
2.5
AL2L
LOW THRESHOLD BAND ALARM AL2
-199.0
AL2H
HIGH THRESHOLD BAND ALARM AL2
999.0
HAL2
ALARM AL2 HYSTERESIS
0.5
AL2d
ACTIVATION DELAY OF ALARM AL2
OFF
AL2i
ALARM AL2 WHEN MEAS ERROR
no
GROUP
כ
AL3 (RELATIVE TO ALARM AL3)
0AL3
OUTPUT, ALARM AL3 ADDRESSED
Out4
AL3t
ALARM AL3 TYPE
HidE
Ab3
ALARM AL3 FUNCTIONING
0
AL3
ALARM AL3 THRESHOLD
4.5
AL3L
LOW THRESHOLD BAND ALARM AL3
-199.0
AL3H
HIGH THRESHOLD BAND ALARM AL3
999.0
HAL3
ALARM AL3 HYSTERESIS
0.5
AL3d
ACTIVATION DELAY OF ALARM AL3
OFF
AL3i
ALARM AL3 WHEN MEAS ERROR
no
GROUP
כ
Lba(RELATIVE TO LOOP BREAK ALARM)
OLbA
OUTPUT LBA ADDRESSED
OFF
LbAt
TIME TO ACTIVATE ALARM LBA
OFF
GROUP
כ
rEG(RELATIVE TO CONTROL)
Cont
CONTROL TYPE
On.FA
Func
FUNCTIONING MODE O/PUT 1rEG
HEAt
HSEt
HYSTERESIS ON/OFF CONTROL
0.5
SLor
GRADIENT OF RAMP RISE
1nF
dur.t
DURATION TIME
1nF
SLof
GRADIENT OF RAMP FALL
1nF
GROUP
כ
Pan (RELATIVE TO USER INTERFACE)
Usrb
FUNCTIONING OF KEY U
noF
diSP
VAR VISUALISED ON DISPLAY
dEF
AdE
SHIFT INDEXING FUNCTION
OFF
Edit
FAST PROG ACTIVE SET POINT & ALARMS
SAE