background image

 68235.06 

 Electrical Connections: 

 Unscrew the four cover screws and lift off the outer cover 

 . 

 CAUTION: 

 Make   sure   the   wires   do   not   obstruct   the 

 function of the switch mechanism. 

 AVERTISSEMENT: 

 Assurez-vous   que   les   fils   ne   sont 

 pas   entraver   le   fonctionnement   de   la   changer   le 
 mécanisme. 

 Diagrams showing the internal connections of the micro-switch with: 

 Flow   switch   used   to   activate   a   device  when 
 flow   stops.   When   the   decreasing   operating 
 flow   is   reached   or   stops   the  common  (black 
 wire)   and   the   normally   open   (red   wire) 
 contacts  open,  while  the  common  (black  wire) 
 and   the   normally   closed   (blue   wire)  contacts 
 close. 

 Flow  switch  is  used  to  activate  a  device  when 
 flow   starts.   When   flow   starts   and   the 
 increasing   operating   flow   is   reached   or 
 exceeded,   the   common   (black   wire)   and 
 normally   open  (red  wire)  contacts  are  closed, 
 while   the   common   (black   wire)   and   the 
 normally closed (blue wire) are open. 