The following instructions must be read prior to the installation of a Caleffi 521201A SinkMixer thermostatic 
mixing valve. The installer should also be aware of his responsibility and duty of care to ensure that all 
aspects of the installation comply with current regulations and legislation. The Caleffi 521201A should 
be installed using the appropriate standard, code of practice and legislation applicable to each state and 
following the details in this manual. The Caleffi 521201A series must be installed by a licensed plumber.
Prior to the installation of the Caleffi 521201A valve, the system must be checked to ensure that the 

system operating conditions fall within the recommended operating range of the valve, i.e. 
verify supply temperatures, supply pressures, risk assessments, etc.

The supply system into which the Caleffi 521201A is to be installed must be thoroughly flushed and 
cleaned to remove any debris which may accumulate during the installation. Failure to remove any debris 
will affect the performance and the manufacturer’s warranty on the product. In areas that are subject to 
high levels of aggressive water, provision must be made to treat the water prior to it entering the valve.

The valve is recommended to be installed in a position orieinted with the cover to the right with cold inlet/
outlet on the right side (allowing direct connection to the sink’s cold water inlet fitting) resulting in the hot 
inlet/mix outlet on the left aligning direct to the hot water inlet sink fitting. It is essential that the access to 
the valve is not obstructed for future maintenance that may be required to the valve or associated fittings.

It is essential that when the installation is designed and/or installed, all current legislation is noted, e.g. the 
maximum distance from the outlet of the valve to any terminal fitting.

The connecting hot and cold water supplies must be connected to the valve strictly in accordance with 
the indications on the body of the valve. The inlets of the valves are clearly marked with the letter H (Hot) 
and C (Cold). The outlet is marked with the word MIX. The valve has male 3/8” compression threads for 
conection to standard 3/8” compression faucet connectors and stops. 

Where one or both the incoming supply pressures are excessive, a Caleffi pressure reducing valve should 
be installed to reduce the pressure(s) within the limits.

The Caleffi 521201A valve is supplied complete with the check valves at the hot and cold inlets.

Mount the 521201A valve to the wall underneath the sink with black plastic mounting bracket supplied 
with valve but not attached. Use mounting screw to attach the mounting bracket to the valve to meet 
the orientation described above. Break off the adjustment key for adjusting the termperature, see 
commisioning section. 

To ensure that the performance of the Caleffi 521201A valve is maintained (in the event of cold water 
failure), the temperature of the hot water supply at the point of entry to the valve must be a minimum of 
18°F higher than the set mixed water discharge temperature.

If the valve is not installed correctly, it will not function correctly and may put the user in danger.

7

Summary of Contents for SinkMixer 521201A

Page 1: ...w rate for stable operation 0 35 gpm 1 3 l min Certifications 1 ASSE 1070 CSA B125 3 2012 certified by ICC ES file PMG 1358 2 NSF ANSI 372 2011 Drinking Water Systems Components Lead Content Reduction...

Page 2: ...t such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions When...

Page 3: ...tpasinstall mis en service et entretenu correctement selon les instructions contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer...

Page 4: ...nd cold water in such a way as to maintain constant set temperature of the mixed water at the outlet A thermostatic element is fully immersed into the mixed water This element then contracts or expand...

Page 5: ...sink and under counter applications in accordance with installation rules and indications specified in ASSE 1070 standards The system must be sized taking into account the current legislation with reg...

Page 6: ...m in case of external distribution its update and validity must be checked at any need Hand changes are forbidden Questodocumentonon daritenersiimpegnativo Ciriserviamoildirittodimodificareinostriprod...

Page 7: ...to the hot water inlet sink fitting It is essential that the access to the valve is not obstructed for future maintenance that may be required to the valve or associated fittings It is essential that...

Page 8: ...Installation diagram COLD HOT 8 Point of use...

Page 9: ...to simultaneous demand 5 Once the supply temperatures are stabilized and the normal operating conditions are established the valve can be commissioned The temperature setting can be adjusted by with t...

Page 10: ...D C O L D H O T M I X Remove 1 4 hex key from mounting bracket Remove white cap Adjust temperature setting with 1 4 hex key After adjustment lock the temperature with locking nut Replace cap and store...

Page 11: ...following steps are checked to maintain optimum valve performance Use the folllowing recommended procedure 1 On the Caleffi 521201A valves the inlet strainers on both the hot and cold water inlet port...