Function

The  SATK  Heat  Interface  Unit  (HIU)  independently  controls  the

heating  and  domestic  hot  water  generation  in  an  individual

apartment within a centralised boiler or district heating system.

Product Range

SATK15313 ABC HIGH  temperature  wall-mounted  HIU 

instantaneous production of DHW, mechanical 

regulation with 30 kPa DPCV.

Technical specifications

Materials

Frame: 

steel plate

Exchanger: 

brazed

Connection pipes: 

copper

Components: 

brass EN12165 CW617N

Performances

Medium: 

water, max. 30% glycol

Maximum medium temperature: 

85°C

Max. pressure: 

- primary circuit: 

PN 10 bar

- domestic hot water circuit:  PN 10 bar

DHW exchanger capacity: 

40 kW

Domestic hot water flow rate: 

min. 1,8 ± 0,3 l/min

max. 18 l/min

HIU connections:

Primary circuit: 

3/4” M

Heating circuit: 

3/4” M

DHW circuit: 

3/4” M

Box contents:

- HIU

- instructions

- fixing screws

- DPCV 30 kPa 

Weight

code SATK15313 ABC: 

8 Kg

Wall-mounted Heat Interface Unit - HIU
Instantaneous domestic hot water production - Mechanical control

SATK15313 ABC

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Dimensions

Characteristic components

Primary circuit flow

Primary circuit return

Domestic hot water outlet

Flow heating circuit

Return heating circuit

Domestic cold water inlet

å ç

é è

ê

78231EN

www.caleffi.com

© Copyright 2013 Caleffi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 - DHW Differential pressure priority valve

2 - Manual air vent

3 - 40 kW Brazed exchanger

4 - Mechanical modulating valve with 

manual pre-set

5 - DPCV (differential pressure

control valve) 

6 - Heat meter template spacer