background image

1

Function 

The  SATK  series  HIU  allows  independent  control  of  heating  and

domestic hot water production within centralised heating systems.

Technical specifications

Materials

Frame: 

galvanised steel

Heat exchanger: 

braze welded stainless steel

Fitting pipes:

copper

Components: 

brass EN 12165 CW617N

Performance

Medium: 

water, max. 30% glycol

Maximum medium temperature: 

85°C

Maximum operating pressure:  - primary circuit: 

10 bar

- domestic hot water circuit:  10 bar

Nominal DHW heat exchanger net output: 

40 kW

DHW circuit flow rate: 

min 1,8 ± 0,3 l/min

max 18 l/min

Hydraulic characteristics: primary/heating circuit:

kv 2,9

Weight:

6 kg

Component specifications

Connections: 

- primary circuit: 

3/4” M

- heating circuit: 

3/4” M

- domestic hot water circuit:  1/2” M

Contents of pack:

- HIU

- Instruction sheet

Key to symbols

Primary circuit flow

Primary circuit return

DHW out

Secondary circuit flow

Secondary circuit return

DCW in

Wall-mounted heat interface unit, instantaneous domestic hot water production

SATK12313

INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

©  Copyright  2014  Caleffi

78228EN

www.caleffi.com

Characteristic components

1 - DHW priority valve

2 - Manual by-pass

3 - 40 kW brazed heat exchanger

The  DHW  priority  valve  (1)  controls

priority of the production of domestic hot

water  in  the  presence  of  a  DHW  circuit

demand.

The heating circuit is always active when

there is no DHW tapping; we recommend

the  use  of  a  zone  valve  or  thermostatic

valve on the heating circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

350

28

G

C

3/4”

88

I

B

194,5

93

H

1/2”

58

D

L

100

65

E

M

163

134

F

N

A

B

C

E

D

I

F

H

N

M

I

I

I

L

L

E

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions