LEGIOMIX Station sizing and selection procedure

3

A. Obtain the maximum GPM (demand) of domestic hot water from project documentation.

B. Select station size which has a Max GPM value equal to or greater than the project maximum GPM demand.

(1) The maximum GPM rating for the LEGIOMIX station is based on 5 feet per second pipe velocity in the station's 

copper tubing. This velocity recommendation is for water temperatures up to 140°F and is from the UPC (Uniform 

Plumbing Code) and the CDA (Copper Development Assocation) "Copper Tube Handbook". To minimize the 

potential of erosion-corrosion in the station piping, do not exceed 5 fps velocity.

(2) The PSI/GPM table is for reference only, showing various GPM values at various pressure drops across the 

station.

Pressure drop across station (PSID)

1

1.5

2

3

5

7.5

Station size

2Flow rates (GPM) @ above pressure drop

1"

7.8

9.5

11.0

13

17

21

1¼"

9.0

11

13

16

20

25

1½"

20

24

28

34

44

54

2"

38

47

54

66

85

105

2½"

43

52

60

74

96

117

Station Code

Station Size

1Max. GPM  

(@ 5 fps pipe 

velocity)

Station Cv

6000

66AS

1"

14

7.8

6000

76AS

1¼"

20

9

6000

86AS

1½"

29

20

6000

96AS

2"

50

38

6000

60AS

2½"

76

43