9
1)
Fully tighten the drain cock on the lower thread of the end cap
and the pocket for the temperature gauge on the front thread.
2)
Tighten the steel rods to the end stop.
6)
Hand thread the furnished screws several turns into the rear
threads: do not tighten them to the end stop since they are the
anchor point between the manifold and the brackets.
3)
Insert a seal and a manifold body on the rods, using the studs
as a reference: the studs on each module should be aligned
with the end cap.
4)
After having inserted the same number of modules to match the
number of outlets, assemble the manifold with seal, closure
plate with grooves facing the inside, and the tightening nuts.
MODULAR MANIFOLD
The distribution manifold has been designed so that it is easy to
mount on a bench.
Since the manifold is reversible, it can be mounted with the main
connections on the right or left depending on the heat pump
position.
The following instructions refer to the manifold with right-side
connections, although it is also possible to mount the left-side
version following the same procedure.
7)
Close the insulation and fit the air vent snugly into the upper
connection.
NOTE:
With a higher number of outlets it may be necessary to
repeat the tightening sequence several times.
5)
To tighten the nuts follow the
adjustment diagram shown
opposite with the following
procedure:
- tighten with torque wrench
to 5 N·m.
- retighten with torque wrench
to 5 N·m.
right-side version
left-side version