SAT102

heat interface unit

7

Maintenance

All  maintenance  procedures  should  be  carried out  by  an  authorised
technician.

Regular maintenance guarantees better efficiency and helps to save
energy.

Before carrying out any maintenance, repair or part replacement work,
proceed as follows:

Switch off the electricity supply

Close the isolation valves

Drain the HIU using the drain cocks provided.

Heat exchanger replacement

To remove the heat exchanger, loosening the 2 socket head screws 
holding it in place (A)

Replace the heat exchanger and the O-rings.

Re-tighten the 2 fixing screws (A) to a maximum torque of 3Nm.

N.B.

The pins fixing the heat exchanger are positioned in such a way as

to prevent it being fitted incorrectly.

Temperature probe replacement

Disconnect the probe cable, lightly folding the tab (C) and 
extracting the connector.

Unscrew the probe.

Fit the new probe.

Re-fit the connector respecting the only possible way it can be 
inserted.

Replacing the valve actuator

Disconnect the actuator cable, lightly pressing the tab on the 
connector and extracting it.

Extract the fixing clip (D) and then the actuator.

Position the new actuator (E).

Insert the fixing clip, respecting the correct direction.

Re-connect the connector.

Replacing the valve obturator

Disconnect the valve actuator - see previous section.

Unscrewing the lock nut (F) and extract the obturator.

Replace the obturator and then refit the lock nut (F).

Insert the fixing clip, respecting the correct direction.

Re-connect the connector.

Replacing the DHW priority flow meter

Disconnect the flow meter cable from the connector.

Extract the flow sensor (G).

Position and fit the new sensor.

Re-connect the cable respecting the only possible way it can be 
inserted.

G

F

D

E

C

A

A

Summary of Contents for altecnic SATK102

Page 1: ...SATK102 heat interface unit Installation Operation Maintenance Instructions...

Page 2: ...e suitable provision for ltering and treating the water before it enters the device in accordance with current legislation Failure to do so may result the HIU becoming damaged or working incorrectly 8...

Page 3: ...o be removed always disconnect the earth connection after disconnecting the electric supply Check that the earth connection has been made to the highest of standards under current legislation 6 Electr...

Page 4: ...ntroller 3 Pump SATK1020X SATK1020X HE 4 DHW temperature sensor and strainer 5 Flow temperature pocket probe 6 Energy meter spool piece 7 Plate heat exchanger 8 Flow switch 9 Modulating primary contro...

Page 5: ...or blocks mobile dividing panels or any masonry walls other than those indicated a preliminary static test must be carried out on the support system Isolation Valves Depending on the speci cation orde...

Page 6: ...eters and settings depending on the model There are a number of speci c DIP SWITCHES on the controller circuit board the way these are con gured will determine the functions enabled Automatic controll...

Page 7: ...turned off Domestic water generation Domestic water preheating function The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if t...

Page 8: ...ct the probe cable lightly folding the tab C and extracting the connector Unscrew the probe Fit the new probe Re t the connector respecting the only possible way it can be inserted Replacing the valve...

Page 9: ...if necessary Screw the cartridge back into position Re position the ow sensor When carrying out maintenance on the electrical part for the connections follow the diagram on page 8 After concluding mai...

Page 10: ...4 5 6 1 2 3 4 5 7 6 L N Electric supply 230 V ac 10 50 Hz 1 DHW temperature probe 2 3 4 5 6 7 DHW flow meter DHW modulating valve actuator Earth Pump Fuse Power Supply 230 V ac X X X X X X X X X X X X...

Page 11: ...d temperature DHW led on domestic water cycle temperature set point too low increase set point HIU strainer clogged call quali ed personnel to have it serviced exchanger partly clogged call quali ed p...

Page 12: ...K102 heat interface unit Altecnic Ltd Mustang Drive Stafford Staffordshire ST16 1GW T 44 0 1785 218200 E sales altecnic co uk Registered in England No 2095101 altecnic co uk IOM 069 09 12 16 E O E Not...

Reviews: