background image

For the brass DIRTMAG

®

the ferrous impurities 

are captured by a strong 

neodymium rare-

earth 

magnetic field created by a powerful 

removable magnet around the body below 
the flow line. 

11

Troubleshooting

System failures are not always caused by the 

pressure reducing valve. Most frequently:

1.  Increased downstream pressure in the 

presence of a water heater 

 If the downstream pressure increases   

beyond the desired setting due to an 

inline water heater, install an expansion 

tank between the pressure reducing 

valve and the water heater to absorb 

the increased pressure, caused by 

water expansion from heating.

 

2.The pressure reducing valve does not

   maintain downstream setting value

 If the pressure reducing valve does 

not maintain the downstream setting, it most likely is due to  impurities acccumulating 

on the valve seat, causing unnecessary flow to pass-through, increasing the downstream 

pressure. Proper maintenance and cleaning of the removable cartridge is recommended.

Summary of Contents for 5353H Series

Page 1: ...r systems that may contain sediment and debris The valve is ICC ES certified to ASSE 1003 CSA B356 NSF 61 NSF 372 low lead laws and listed by ICC ES It meets codes IPC IRC and UPC for use in accordanc...

Page 2: ...maintenance of the 535H PRV take the necessary precautions to ensure that such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be u...

Page 3: ...en service et l entretien de le r ducteur de pression S rie 535H prendre les precautions n cessaires afin de s assurer que de tells temp ratures ne compromettent pas les gens LAISSEZ CE MANUEL AVEC L...

Page 4: ...ange 15 90 psi 1 6 bar Factory setting 45 psi 3 bar Max working temperature 180 F 80 C Pressure gauge scale 0 100 psi 0 7 bar Filter mesh size 0 51 mm 35 mesh Suitable fluids water Main connections NP...

Page 5: ...1 2 3 4 1 1 1 1 4 1 1 2 2 0 45 5 V m s 0 1 4 3 0 3 1 1 4 535074 5 1 1 1 4 1 2 3 4 1 2 5 0 2 10 20 20 50 00 Flow rate min m 3 h 00 5 10 1 5 V f s 0 3 15 10 1 8 20 90 Flow rate s gpm 30 40 10 5 2 1 0 9...

Page 6: ...noise in the pipes and rapid wear of appliances The correct diameter of the pressure reducing valve is taken from graph 1 on the basis of the design flow rate taking into account an ideal flow velocit...

Page 7: ...to the required value in the system prior to installation The pressure indicator features incremental step movement so that the pressure can be adjusted continuously and the value displayed at 15 psi...

Page 8: ...is highly recommended to refer to the working conditions represented in the above diagram Due to the numerous factors and variable conditions experienced such as system pressure water temperature air...

Page 9: ...llation of valve and permitting quick change out from the jumper to the valve Code Description Face to Face Dimension NA11304 Jumper nipple for 535H series 3 NA11305 Jumper nipple for 535H series 3 9...

Page 10: ...s pre assembled as a self contained unit with a cover and can be removed for inspection and maintenance When checking cleaning or replacing the cartridge 1 Shut off the inlet and outlet isolation valv...

Page 11: ...etween the pressure reducing valve and the water heater to absorb the increased pressure caused by water expansion from heating 2 The pressure reducing valve does not maintain downstream setting value...

Page 12: ...Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 12 Leave this manual at the service of users for their use 04 20 18...

Reviews: