6
en
WARNING!
Electric shock!
Upon opening the housing, live parts are exposed!
Î
Always disconnect the device from power supply be-
fore opening the housing!
The device is protected by a fuse. The fuse holder (which also holds the spare fuse)
becomes accessible when the cover is removed. To replace the fuse, pull the fuse
holder from the base.
Operating control
LED
flashes red.
Sensor fault.
°C
Ω
Pt1000
°C
Ω
Pt1000
-10
961
55
1213
-5
980
60
1232
0
1000
65
1252
5
1019
70
1271
10
1039
75
1290
15
1058
80
1309
20
1078
85
1328
25
1097
90
1347
30
1117
95
1366
35
1136
100
1385
40
1155
105
1404
45
1175
110
1423
50
1194
115
1442
Short circuit or line break.
Disconnected temperature sensors can be checked
with an ohmmeter. Please check if the resistance values
correspond with the table.
3 Troubleshooting
Fuse
Summary of Contents for 161020
Page 7: ...7 en...