WARNING!

Electric shock!
Upon opening the housing, live parts are exposed!

 

Î

Always disconnect the device from power supply be-
fore opening the housing!

The device is protected by a fuse. The fuse holder (which also holds the spare fuse) 
becomes accessible when the cover is removed. To replace the fuse, pull the fuse 
holder from the base.

Operating control 

LED

 flashes red.

 

Sensor fault. 

°C

Ω

Pt1000

°C

Ω

Pt1000

-10

961

55

1213

-5

980

60

1232

0

1000

65

1252

5

1019

70

1271

10

1039

75

1290

15

1058

80

1309

20

1078

85

1328

25

1097

90

1347

30

1117

95

1366

35

1136

100

1385

40

1155

105

1404

45

1175

110

1423

50

1194

115

1442

Short circuit or line break.

Disconnected temperature sensors can be checked 
with an ohmmeter. Please check if the resistance values 

correspond with the table.

3  Troubleshooting