The front panel of the controller shows the following functions:

1)

The LED is lit when there is a risk of condensation forming 
in the cooling function (the mixing valve is closed).

In the heating function, this lights up intermittently during the
screed drying phase.

2)

The LED is lit in the cooling function.

3)

The LED is lit in the heating function.

4)

Pump operating (ON): LED lit continuously.

5)

Mixing valve closing: LED lit. The LED is lit continuously 
when the controller is in the non-operative phase of 

regulation, for example with T

Outside

between 18°C and 24°C 

(see characteristic curve).

6)

Mixing valve opening: LED lit.

7)

Sensor malfunction: LED lit.

8)

Function selector, 6 different functions possible:

a)

Main controller off. In models where clock fitted, clock 
remains on. The frost protection function remains active. 

b)

Controller operating in set-back mode.
Has no effect on the cooling function.

c)

Controller operating in comfort mode.
Has no effect on the cooling function.

d)

Controller in operation according to the cycles of the 
comfort or set-back modes, determined by the two-channel 

analogue clock, red indicator for heating times, blue indicator
for cooling times (item 13).

e)

Controller de-activated (pump ON - mixing valve ON).
This function guarantees heating to the maximum 
temperature value set on the printed circuit board (PCB).

Has no effect on the cooling function.

f)

Summer function. Cooling is activated if required by the 
ambient conditions (T

Outside

greater than the value set at

point 10) and dependant on the clock settings.This activation 
takes place after ten minute if the outside temperature is more
than 1°C above the set value. With the exclusion of heating, the 
frost protection function remains active.

Note:

Normally, with the clock programme, the changeover from 

heating to cooling takes place after the outside temperature has
been higher than the set value for at least half an hour. This 
selector position can therefore be used to effect a changeover
to cooling.

9)

Temperature and characteristic curve selector. This
selector enables the user to input the maximum required 

flow temperature, corresponding to the minimum 
outside design temperature. Also enables optimisation of the 
standard configuration set at the factory, allowing personal 
control of the operation of the system.
If this value matches the setting on the main printed circuit 
board (item 6 PCB), the regulation complies with the calculation
criteria given by the characteristic curve.
If this value is different from the setting on the main printed 
circuit board (item 6 PCB) the controller will recalculate the new 
characteristic curve. The maximum set temperature, however, 
remains active. This selector also determines the characteristic 
cooling curve, as it uses the inclination of the first line of the 
curve, constructed for the heating (see characteristic curve graph).

10)

Start or stop cooling selector. If the outside temperature 
is higher than the set value, the cooling function is activated. 

Factory setting: 24°C.

Characteristic curve

The characteristic curve is determined taking into account the
following parameters:

a)

Max flow temperature set on controller (item 9 PCB).

Factory setting: 45°C.

b)

Min flow temperature set on printed circuit board (item 5 
PCB). 

Factory setting: 20°C.

c)

Min outside temperature set on printed circuit board (item 
1 PCB). 

Factory setting: -10°C.

d)

Outside temperature limit for heating start in summer,
set on printed circuit board (item 3 PCB).

Factory setting: 18°C.

The characteristic curve has a straight line format.
In the example shown below, it has been calculated using the
factory set values.

Example of calculation of characteristic curve

X Axis - 

Outside temperature - TX

Y Axis - 

Flow temperature - TY

Calculation of minimum and maximum points

Point A: given by the intersection of Tmax X (18°C) and Tmin Y (20°C).
Point B: given by the intersection of Tmin X (-10°C) and Tmax Y (45°C).

Calculation of slope change points

Calculate the difference 

X between Tmax X and Tmin X.

Thus: 

X = 18 - (-10) = 28°C.

Calculate the difference 

Y between Tmax Y and Tmin Y.

Thus: 

Y = 45 - 20 = 25°C.

Points of change C and D of the curve are identified as follows:

Point C given by the intersection between:
X = Tmax X - 25% 

X = 18 - 0,25 · 28 = 11°C

Y = Tmin Y + 55% 

Y = 20 + 0,55 · 25 = 33,75°C

Point D given by the intersection between:
X = Tmax X - 50% 

X = 18 - 0,5 · 28 = 4°C

Y = Tmin Y + 80% 

Y = 20 + 0,8 · 25 = 40°C  

Point E is the cooling starting point, whose characteristic curve has
the same slope as section A-C.
Point E given by the intersection between: TX = value set in item 10
(24°C) and TY = Tmin Y (20°C).

Characteristic curve

5

20

25

30

35

40

45

50

55

60

35

20

15

10

5

0

-5

-10

-15

T

FLOW

 (

°

C)

T

OUTSIDE

 (

°

C)

A (18;20)

C (11;33,75)

D (4;40)

B (-10;45)

80%

55%

50%

25%

15

10

25

30

E (24;20)

Passive band

Summary of Contents for 152 Series

Page 1: ...88 03 GB Function The temperature regulating unit is designed to guarantee the correct contribution of heating energy required by the user by measuring the outside and room temperature values to regul...

Page 2: ...25 60 code 152651 GRUNDFOS UPS 25 80 04 Differential by pass valve with graduated scale 05 Flow temperature sensor 06 Outside temperature sensor connected via terminal 07 Circuit flow and return therm...

Page 3: ...personal control of the operation of the system If this value matches the setting on the main printed circuit board item 6 PCB the regulation complies with the calculation criteria given by the chara...

Page 4: ...actory setting 18 C An outside temperature higher than the set value will cause the following state circulator OFF and mixing valve closed An outside temperature 4 C higher than the set value will cau...

Page 5: ...the primary It can be used to shut down the pump of the primary circuit or the boiler 10 UR Relative humidity sensor wiring This sensor is used to detect the limiting value of relative humidity to pr...

Page 6: ...imit sensor Safety If the flow or outside sensor shows an ohm resistance value outside its working range damaged or disconnected sensor the following operating state is automatically activated Pump OF...

Page 7: ...rence between the actual room temperature measured by the thermostat and the set temperature produces an amplified effect in relation to that produced by a similar variation in the outside temperature...

Page 8: ...ics power supply 230 V 50 Hz rating 10 VA cycle time 240 s torque 10 N m Pump UPS 25 80 By pass valve with regulating scale from 0 05 channel clock for daily weekly programming Flow temperature sensor...

Reviews: