INstAllAtION, OpeRAtION ANd MAINteNANce INstRuctIONs
Commercial CondenSAFE units are designed to optimize raw condensate
fl ow. A double walled reactor features additional buff er volume for
preneutralization. Preneutralized conden sate fl ows up vertically through
the reactive media. (Fig. 1) Screw the connectors or the unions onto
each of the unit’s connections. The CondenSAFE inlet is situated on the
MNPT side. It is important to connect the boiler’s drain outlet to your
CondenSAFE unit’s inlet to ensure optimal treat ment of the condensate.
Connect a pipe at the CondenSAFE unit’s outlet and make sure the
neutralized condensate is directed safely towards the buildin’s drain.
Do not allow the piping to pass through areas which could be exposed
to temperatures below the freezing point. Ensure that the piping has a
suffi
cient incline to let the fl uid fl ow to the drain by gravity.
Each unit is supplied with 4.6 kg of media capable of treating the conden-
sate equivalent to that of a 3500 MBH (1026 kWh) unit, appro ximately
28 gallons (106 liters) per hour. To increase CondenSAFE’s treatment
capacity, you can install up to 3 units in series using the union kit sold
separately (#CSCUK).
At the beginning and end of the heating season, verify the acidity of
the effl
uent treated by CondenSAFE using test strips. Test strips are
available at your local dealer (#CSPH). Contact local authorities to verify
the reglementation regarding the authorized acidity level of effl
uent
(drain or septic tank). Replace the media (#CSM28)at least once per
year, or as soon as the acidity level of the effl
uent no longer meets
local norms.
INstRuccIONes de INstAlAcIóN, OpeRAcIóN Y MANteNIMIeNtO
Atornille los conectores o uniones a cada extremo de la unidad. La entrada
de la unidad CondenSAFE está ubicada en el extremo MNPT (conexión
macho) y la salida en el extremo FNPT (conexión hembra). Es importante
conectar la salida del drenaje de la caldera a la entrada del CondenSAFE
para asegurar el óptimo tratamiento del condensado. Las unidades
comerciales CondenSAFE están concebidas para optimizar el modo de
evacuación del condensado bruto. El reactor de doble pared ofrece un
volumen tampón para la preneutralización. El condensado preneutralizado
atraviesa verticalmente de manera ascendente todo el medio reactivo
(Fig.1). Conecte un tubo a la salida de la unidad CondenSAFE cuidando
de dirigir de modo seguro el condensado neutralizado hacia el drenaje
del edifi cio. No haga pasar el tubo de drenaje por un lugar expuesto a
temperaturas por debajo del punto de congelación. Asegúrese que la
cañería esté lo sufi cientemente inclinada como para permitir al efl uente
descargar hacia el drenaje por efecto de la gravedad.
Cada unidad está provista de 4.6 kg de medio condensante, lo que
permite tratar el equivalente del condensado de un equipo de 3500 MBH
(1026 kWh), aproximadamente 28 galones (106 litros) de condensado
por hora. Para aumentar la capacidad de tratamiento del CondenSAFE
es posible instalar hasta tres unidades en serie con ayuda de un equipo
de unión que se vende por separado (#CSCUK).
Québec (Canada)
T
450 951.0818
F
450 951.2165
calefactio.com
INS
T-C
SC28-
20
16-0
3-
TRI
Fig. 1
Verifi que la acidez del efl uente tratado por CondenSAFE al principio y al
fi nal de cada temporada de calefacción. Su proveedor puede procurarle
tiras reactivas para la medición del pH (#CSPH). Verifi que ante las
autoridades locales la reglamentación sobre la acidez autorizada del
efl uente (drenaje o sistema séptico). Reemplace el medio (#CSM28) al
menos una vez al año o cuando la acidez del efl uente no cumpla con las
normas locales.
INstRuctIONs d’INstAllAtION, OpÉRAtION et eNtRetIeN
Les unités CondenSAFE commerciales sont conçues de façon à optimiser
le mode d’écoulement du condensat brut. Le réacteur à double paroi off re
un volume tampon pour pré neutralisation. Le condensat pré-neutralisé
traverse verticalement d’une façon ascendante tout le média réactif.
(Fig. 1) Vissez des connecteurs ou des unions à chaque embout de l’unité.
L’entrée de l’unité CondenSAFE est située du côté MNPT et la sortie du
côté FNPT. Il est important de brancher la sortie du drain de la bouilloire
dans l’entrée de l’unité CondenSAFE afi n d’assurer le traitement optimal
du condensat. Branchez un tuyau à la sortie de l’unité en prenant soin
de diriger le condensat neutralisé vers le drain du bâtiment de façon
sécuritaire. Ne faites pas passer le tuyau à un endroit qui peut être exposé
à des températures sous le point de congélation. Assurez-vous que la
tuyauterie est suffi
samment inclinée afi n de permettre au débit de couler
vers le drain par gravité.
Chaque unité est fournie avec 4,6 kg de média, qui peut traiter l’équi-
valent du condensat d’un appareil de 3500 MBH (1026 kWh), soit environ
28 gallons (106 litres) de condensat par heure. Pour augmenter la
capacité de traitement de CondenSAFE, il est possible d’installer jusqu’à
trois unités en série à l’aide de l’ensemble d’union vendu séparément
(#CSCUK).
Vérifi ez l’acidité de l’effl
uent traité par CondenSAFE en début et fi n de
saison de chauff age. Des languettes de test sont disponibles auprès
de votre détaillant (#CSPH). Vérifi ez la réglementation pour l’acidité
autorisée à l’effl
uent (drain ou système septique) auprès des autorités
locales. Remplacez le média (#CSM28) au moins une fois l’an, où aussitôt
que l’acidité de l’effl
uent ne rencontre plus les normes locales.
OUTLET
SALIDA
SORTIE
INLET
ENTRADA
ENTRÉE
THE CONNECTION BETWEEN THE HEATING AND
CONDENSAFE UNITS MUST BE DONE IN SUCH A
WAY AS TO ENSURE THAT THE BACKFLOW DOES
NOT RETURN TOWARDS THE UNIT.
LA CONEXIÓN ENTRE EL CALENTADOR Y LA
UNIDAD CONDENSAFE SE DEBE REALIZAR
DE MANERA QUE EL CONDENSADO NO SEA
ENTREGADO AL DISPOSITIVO.
LE BRANCHEMENT ENTRE L’APPAREIL DE
CHAUFFAGE ET L’UNITÉ CONDENSAFE DOIT
ÊTRE FAIT DE MANIÈRE À CE QUE LE CONDENSAT
NE REFOULE PAS VERS L’APPAREIL.