UNIGUARD UG-2-A2 STAND-ALONE-UNIT

Smoke detector for duct installation.

DIMENSIONS

(mm)

INSTALLATION

The venturi tube is made of aluminium and can easily be 
shortened to suit the diameter of the duct. Hole diameter is 35 
mm. With insulated or circular ducts - use the mounting bracket,  
hole diameter is then 50 mm.

MAINTAINANCE

When the detector becomes contaminated, sensitivity is 
increased, triggering the service alarm. This can be avoided 
for a considerable time by cleaning the detector once a year 
with a vacúum cleaner.

CHECKING AIR FLOW

The detector is equipped with a flow indicator which oscillates 
in the air stream when the detector is correctly installed. This 
gives simple confirmation that there is no leakage, and that air 
from the ventilation duct is flowing through the detector.

FUNCTION TEST

When installation is complete, the detector should be tested. 
This can be carried out with smoke or suitable testspray for 
example RDP-300 (from Calectro), use the test hole on cover. 
D o not forget to refit the plastic plug after test.

NB:  When  installing  outdoors  or  in  cold  attics  etc.,  where 
there is a risk for condensation, this requires that the detector 
is insulated from the surrounding air by means of for example 
our waterproof housing UG-SH,  and marked with an extra 
indicator lamp, LED-01 and a sign marked "Hidden Detector".

FUNCTION

Normal operation: 

In normal operation the alarm relay  

 

is energized, and the relay contacts 

 

are closed between C and NC.

Smoke alarm: 

The LED of the detector is showing 

 

red light and the relay contacts are 

 

changing to C and NO.

Reset: 

After alarm the reset push-button has 

 

to be pressed in order to have the 

 detector 

back 

into normal operation.

Pre-alarm: 

When the detector is sensing smoke or
is dirty the LED of the detector will first 
show green colour before going into 
alarm with red light. If the detector is 
dirty, it will show green light. This is 
an optical indication (a pre-alarm or 
 service-alarm) which means that the 
detector is contamined and if it is not 
cleaned, it will later on give a false 
alarm.

Failure: 

If there is something wrong with the 

 

detector, the alarm relay will change 

 contacts:
 

a) If the detector module is taken away

 

b) If the supply voltage is interrupted

WIRING DIAGRAM

Alarm relay: 

ONE changing contact,

 

max 250V, 2Amp

Note! 
Changing between AC and DC is made by a jumper.

The jumper is factory set to AC.

External
reset button

Supply 24 VADC 100mA (±20%)

Alarm
output

NC

NO

C

= 24 VDC

= 24 VAC