4
Mounting in places where possible condensation problems could arise, e.g. cold attics.
Use protection cover e.g. Calectro´s
UG-COVER-75.
Use insulation cover of 100-200 mm (4-8")
to protect the entire Uniguard.
8
Do not drill any holes in the cover for signs etc.
Holes will cause air leakage and seriously disturb
the function of the detector.
Test of detector
7
TEST
SPRA
Y
1. Check the detector with smoke detector
aerosol test spray (e.g. SOLO A5).
2. Move the "test hole plug" to the side
and briefly release a spray of aerosol.
When alarming, the LED lits red on the
detector and when service alarming
(contamination) it lits green.
IMPORTANT!
Reassemble the "test hole plug".
A sign should be used to show location of the detector.
A remote LED alarm indication is recommended when the Uniguard is hidden.