MODBUS REGISTER FOR IOMB-03

Coils (0x)

Function

Range

0x0001

Digital output #1

Off or On

0x0002

Digital output #2

Off or On

0x0003

Digital output #3

Off or On

Discrete inputs (1x)

Function

Range

1x0004

Digital input #1

Off or On

1x0005

Digital input #2

Off or On

1x0006

Digital input #3

Off or On

Input reg. (3x)

Function

Range

3x0010

Analog input #1 x100 (Volt)

0 to 1000

3x0011

Analog input #2 x100 (Volt)

0 to 1000

3x0012

Analog input #3 x100 (Volt)

0 to 1000

3x0013

Analog input #1 (Ohms)

0 to 1300

3x0014

Analog input #2 (Ohms)

0 to 1300

3x0015

Analog input #3 (Ohms)

0 to 1300

3x0016

Analog input #1 x10 (°C)

-50 to +50

3x0017

Analog input #2 x10 (°C)

-50 to +50

3x0018

Analog input #3 x10 (°C)

-50 to +50

Holding reg. (4x)

Function

Range

4x0001

Digital output #1

0 or 1

4x0002

Digital output #2

0 or 1

4x0003

Digital output #3

0 or 1

4x0004

Digital input #1

0 or 1

4x0005

Digital input #2

0 or 1

4x0006

Digital input #3

0 or 1

4x0007

Analog output #1 x100 (Volt)

0 to 1000

4x0008

Analog output #2 x100 (Volt)

0 to 1000

4x0009

Analog output #3 x100 (Volt)

0 to 1000

4x0010

Analog input #1 x100 (Volt)

0 to 1000

4x0011

Analog input #2 x100 (Volt)

0 to 1000

4x0012

Analog input #3 x100 (Volt)

0 to 1000

4x0013

Analog input #1 (Ohms)

0 to 1300

4x0014

Analog input #2 (Ohms)

0 to 1300

4x0015

Analog input #3 (Ohms)

0 to 1300

4x0016

Analog input #1 x10 (°C)

-500 to +500

4x0017

Analog input #2 x10 (°C)

-500 to +500

4x0018

Analog input #3 x10 (°C)

-500 to +500

4x0019

Digital output #1 default 

value

*

1

0 or 1

4x0020

Digital output #2 default 

value

*

1

0 or 1

4x0021

Digital output #3 default 

value

*

1

0 or 1

4x0022

Analog output #1 default 

value x100 (Volt)

*

1

0 to 1000

4x0023

Analog output #2 default 

value x100 (Volt)

*

1

0 to 1000

4x0024

Analog output #3 default 

value X100 (Volt)

*

1

0 to 1000

4x0025

Timeout for activating default 

values (4x0019-4x0024)

*

2

0-600 sec

4x0026

Setting of temperature 

sensor type, analog input 1: 

0=Pt1000, 1=Ni1000LG

0 or 1

4x0027

Setting of temperature 

sensor type, analog input 2: 

0=Pt1000, 1=Ni1000LG

0 or 1

4x0028

Setting of temperature 

sensor type, analog input 3: 

0=Pt1000, 1=Ni1000LG

0 or 1

*1  Selectable default value that can be activated in the event of communica-

tion failure on the Modbus loop.

*2  For communication failures (Modbus) that have lasted longer than the 

number of set seconds (1-600 sec), the adjustable default values   for 

registers 4x0019 to 4x0024 are activated. To turn off the function, select 

0 seconds (factory setting).

MODBUS-COMMUNICATION

Reference  Description

0x

Read/Write Discrete Outputs or Coils

1x

Read Discrete Inputs

3x

Read Input Registers

4x

Read/Write Output or Holding registers