IOMB-TCP/IP INSTALLATION INSTRUCTION

ENGLISH

GATEWAY FOR I/O-MODULES. Fits IOMB-

02, IOMB-03 and IOMB-04.

TECHNICAL DATA
Supply voltage:

 

From the I/O- 

 

modules IOMB-02 

 IOMB-03/IOMB-04

Communication: 

TCP/IP

Connection: 

RJ45

Indications LED on PCB 

  - Yellow, flash:

 

TCP/IP  

 communication

  

  - Yellow, double flash:

  DHCP energising  

 

via push button 

  - Green, fixed:

 Operation 

  - Green, blink:

 

Internal Modbus  

 communication

Ambient temperature: 

-20 till +50°C

Dimensions (WxHxD): 

75x39x33 mm

USE

IOMB-TCP/IP is a gateway for IOMB-02, IOMB-

03 and IOMB-04 that permits communication 

with the I/O modules via TCP/IP.

FUNCTION

The TCP/IP gateway communicates inter-

nally with the I/O module via modbus RTU and 

externally via TCP/IP. In order for the factory-

set Modbus communication to work, all DIP 

switches On the I/O module must be set to 

OFF. You can change the Modbus communica-

tion settings in the web interface for the TCP/

IP gateway, in which case you must also adjust 

the DIP switch settings in the I/O module. 

The TCP/IP gateway has the capacity to com-

municate with one external device (e.g. OPC 

server) at a time.

MOUNTING

The IOMB-TCP/IP is mounted using the 4 screws 

and washers provided, onto the I/O modules IOMB-

02, IOMB-03 or IOMB-04.
By replacing the rubber gasket in the M20 screw in 

the I / O module with the supplied multi-hole gasket, 

a pre-contacted Cat5 / 6 can be used. See Figure 1.
Remove the termination jumper located on the I / O 

module. Please note that the 10-pin strip fits correct-

ly during the assembling. See Figure 2.

INSTALLATION 

The DIP switches (1–10) in the I/O module must be 

in their OFF positions to enable internal communica-

tion between the I/O module and the TCP/IP gateway.

Instruction, connection to network:

1.  Connect the TCP/IP module to the designated 

location on IOMB-02, IOMB-03 or IOMB-04.

2.  Fit the 4 accompanying washers and screws.
3.  Energise the I/O module. The green and yellow 

LEDs on the TCP/IP module light up.

4.  Press the button to the right of the yellow LED and 

hold it down until the yellow LED flashes twice. 

The TCP/IP gateway is now set to receive an IP 

address via DHCP.

5.  Plug in the network cable.
6. To access the network settings, open a web 

browser and search for host name: ”http://calec-

trobrige”. If you experience problems locating the 

TCP/IP gateway, download and install the pro-

gram: “Microchip TCPIP Discoverer” available-

from Calectro’s website: http://www.calectro.se/ 

products/#!/programvaror/. This program looks 

for all connected gateways that have a TCP/IP 

circuit from Microchip and displays their assigned 

IP addresses.

7.  Log in to network settings with the user name: 

“admin” and password: “admin”.

8.  Click NETWORK SETTINGS to access the net-

work settings.

9.  Under MODBUS SETTINGS you can manage 

internal communication between the I/O module 

and the TCP/IP gateway. You do not usually need 

to adjust this. The default settings in MODBUS 

SETTINGS correspond to the I/O module’s DIP 

switch in the OFF position.

MAINTENANCE

IOMB-TCP/IP is maintenance-free.

© 2020.07.07 R1.0   Calectro 

AB   HFE6046

EN

MODBUS-SETTINGS FOR I/O-MODUL

(DIP-SWITCH: 0 = OFF / 1 = ON)

Modbus ID

DIP-switch 

1,2,3,4,5 and 6

1

000000

2

100000

3

010000

4

110000

5

001000

6

101000

7

011000

8

111000

9

000100

10

100100

11

010100

12

110100

13

001100

14

101100

15

011100

16

111100

17

000010

18

100010

...

...

64

111111

Modbus Parity

DIP-switch 7 and 8

None (2 stop bits)

00

None (1 stop bit)

11

Even (1 stop bit)

10

Odd (1 stop bit)

01

Modbus Baud rate

DIP-switch 9 and 10

9600

00

19200

10

38400

01

57600

11