EM_eSENSE_standard_April’03

 

 

2 av 4 

Electrical connections  
 

The power supply has to be connected to G+ and G0. G0 is considered as system ground. The 

same ground reference has to be used for  the 

0

6(16(

®

  unit and for the DDC/signal 

receiver.   
 

PLEASE NOTE! 
The same ground reference has to be used for the 

0

6(16(

®

  

  unit 

and for the control system!

 

 
 

 

Terminal 

 

Function 

 

Elektrical data 

 

Remarks 

 

G+ 

 

G0 

 

Power (+) 

 

Power ground (-) 

 

24 VAC/DC+  (+-20%), 2W 

 

24 VAC/DC-

 

 
 
 
System voltage reference 

 

OUT1 

 

OUT2 

 

 

Analogue output 1 (+) 

 

Analogue output 2 (+) 

 

 

0-10 VDC 

 

2-10 VDC 

0,9-1,1 VDC 

 
0-2000 ppm CO

2

 

 
0-2000 ppm CO

Status = NOT READY or 
ERROR 
 

 

Table I. Connections of the main terminal of 

0

6(16(

®

 

 

 

 

 

 