U
ser
'
s
G
Uide
— 49
finding Motor branch-Circuit Wire size and Conduit size —
Same Wire type and Size
What size THHN Copper Wire and RMC Conduit are needed to
connect a 10 HP 1Ø Induction motor to a 115 Volt source?
KeysTRoKe
DIsPlay
0.
1. Set to 1-Phase:
(1Ø)
1 Ø
1 Ph
2. Set to 60º C:
(60º)
1 Ø 60
1 Ph
3. Set to Copper (if necessary):
(
Cu/Al
)
1 Ø 60 Cu
1Ph
4. Enter Volts:
VolT 115.
5. Enter Horsepower:
InD* 10. hP
*
If
iND
is not shown, press
until
iND
is displayed in the upper left
area of the display.
6. Display Full-Load Amps:
flC 100.
a
7. Find Wire Size at 125% Ampacity:
(125%)
aWG 0 Cu
WIRe sIZe 125%
8. Find Wire Ampacity:
Ø* 125.0
WIRe a125%
*
The Wire Size will be shown in the upper left area of the display when
displaying the Wire Ampacity rating.
9. Enter Conduit Type and find Conduit Size:
(Cond Type)
RMC 1.25 in
ConD sIZe
(cont’d)