23.0
INITIAL START-UP
WARNING:
DO NOT ATTEMPT TO IGNITE HEATER BY HAND!!
IMPORTANT NOTICE:
This heater is not to be used as a construction heater to supply heat to an
unfinished building during the finishing phases of Construction. This practice exposes the unit to an
abnormally corrosive atmosphere from sources such as paint, varnish and adhesives, which can lead
to premature radiant tube exchanger or vent failure. The practice also allows foreign materials such as
sawdust or sheet rock dust to enter the combustion blower, burner, heat exchanger and vent system,
resulting in shorter life of the unit.
Use of the heater as a construction heater will void the warranty.
Procedure:
a)
Make sure gas is turned on.
b)
Check for any possible blockages in combustion air intake and exhaust areas of unit.
c)
Make sure that venting material is properly fastened to the unit.
d)
Make sure all options are attached securely.
e)
Make sure electricity is on to unit.
f)
Turn thermostat up past room temperature.
g)
Check the flame port to see flame has established,
h)
If flame is not established, turn the thermostat down for 5 seconds then turn back up or interrupt
electrical supply to unit for 5 seconds, and allow unit to try again.
i)
Verify that the manifold pressure (outlet pressure tap) on the gas valve is the same pressure as
stated on the rating plate of the unit. Use a manometer that measures inches of water column for
this procedure. If adjustment is required, remove the cap-screw from the pressure regulator housing.
Adjust the white pressure regulator adjusting screw clockwise (in) to increase pressure,
counterclockwise (out) to reduce pressure. Replace cap-screw. After measurement has been taken,
replace pipe plug in outlet pressure tap. Check for leaks. (see pages 3, 4 & 74)
j)
Verify gas input rate. (see page 67)
NOTE:
Oil smoke might appear off of exchanger tube after it heats up for initial firing. Do not be alarmed. The
smoke is just a small amount of oil on the surface of the tube from manufacturing. If smoke is excessive, open
door and 'air out' the building until smoke is removed.
NOTE: Heater will have a higher heat output at the burner end as compared to the exhaust end. This is
normal. See page 5 for details.
NOTE: A small amount of condensation may occur from the heater when it starts the heating cycle. The
condensation will stop once the heater warms up. Make sure venting is sealed according to page 49.
Summary of Contents for SR Series
Page 18: ...SR SERIES 14 PIPE BOXES Figure 11 PIPE BOX CONTENT...
Page 19: ...SR SERIES 15 10 3 M REFLECTOR PACKAGE Figure 12 10 3 M REFLECTOR PACKAGE CONTENTS...
Page 20: ...SR SERIES 16 15 4 16 M REFLECTOR PACKAGE Figure 13 15 4 16 M REFLECTOR PACKAGE CONTENTS...
Page 21: ...SR SERIES 17 20 6 1 M REFLECTOR PACKAGE Figure 14 20 6 1 M REFLECTOR PACKAGE CONTENTS...
Page 22: ...SR SERIES 18 30 9 1 M REFLECTOR PACKAGE Figure 15 30 9 1 M REFLECTOR PACKAGE CONTENTS...
Page 23: ...SR SERIES 19 40 12 2 M REFLECTOR PACKAGE Figure 16 40 12 2 M REFLECTOR PACKAGE CONTENTS...
Page 24: ...SR SERIES 20 50 15 2 M REFLECTOR PACKAGE Figure 17 50 15 2 M REFLECTOR PACKAGE CONTENTS...
Page 25: ...SR SERIES 21 60 18 3 M REFLECTOR PACKAGE Figure 18 60 18 3 M REFLECTOR PACKAGE CONTENTS...
Page 26: ...SR SERIES 22 70 21 3 M REFLECTOR PACKAGE Figure 19 70 21 3 M REFLECTOR PACKAGE CONTENTS...
Page 27: ...SR SERIES 23 80 24 4 M REFLECTOR PACKAGE Figure 20 80 24 4 M REFLECTOR PACKAGE CONTENTS...
Page 28: ...SR SERIES 24 10 3 M EXTENSION KIT Figure 21 10 3 M EXTENSION PACKAGE CONTENTS...
Page 29: ...SR SERIES 25 SIDE REFLECTOR PACKAGE Figure 22 SIDE REFLECTOR PACKAGE CONTENTS...
Page 56: ...SR SERIES 52 SIDE REFLECTOR Figure 52 SIDE REFLECTOR INSTALLATION...
Page 78: ...SR SERIES 74 24 0 GAS VALVES Figure 62 GAS VALVE Figure 63 PRESSURE REGULATOR...
Page 94: ...SR SERIES 90...
Page 95: ...SR SERIES 91...