INSTALLATION INSTRUCTIONS
PLACEMENT: For best results install The Register on an inside wall. Headers and bracing are not necessary. NOTE: The wall can must
be installed in the TOP UP (horizontal) position only. Heater is not approved for ceiling mount.
THERMOSTAT: A thermostat is required. A Cadet Elec tronic Thermostat is recommended for ultimate control and comfort.
REQUIRED MINIMUM distance of 6 inches from adjacent surfac-
es and 4½ inches from the floor (See Figure 4). However, Cadet
RECOMMENDS 12 inches from adjacent surfaces and floor for
longer and cleaner performance. Heaters must be spaced at least
3 feet apart.
Secure the wall can to the studs and/or sill plate with screws
through the larger (3/16 inch) holes. (See Figures 1 and 2).
Cut a hole 12¾ inches wide by 6 inches high next to a wall stud.
REQUIRED MINIMUM distance of 6 inches from adjacent surfac-
es and 4½ inches from the floor (See Figure 4). However, Cadet
RECOMMENDS 12 inches from adjacent surfaces and floor for
longer and cleaner performance. Heaters must be spaced at least
3 feet apart.
Figure 3
Figure 5
Figure 4
Figure 2
Figure 1
Metal legs position wall can
at minimum floor clearance
Bend one leg 90 degrees for
higher placement, and secure
to studs
Face of wall can must extend
½ inch or ⅝ inch from face of
stud to allow for thickness of
sheetrock. Mount wall can flush
with finished surface.
STEP 2
Route Supply Wires
Route supply wire from
circuit breaker to wall
thermostat, then to wall
can. Remove a knockout
and attach the supply wire
with a strain relief connec-
tor leaving 10 inches wire
lead for later use (See
Figure 5). Connect sup ply
ground wire to ground ing
pigtail in wall can.
1.
WARNING
Verify that the electrical supply wires are the same
voltage as the heater.
2. If replacing an existing heater, check the label
of the old heater.
3. All electrical work and materials must comply
with the National Electric Code (NEC), the Occu-
pational Safety and Health Act (OSHA), and all
state and local codes.
4. If you need to install a new circuit or need addi-
tional wiring information, consult a qualified elec
-
trician.
5. Use copper conductors only.
6.
WARNING
Risk of Electrical Shock. DO NOT install the heat-
er directly above bathtub or sink. DO NOT install
in shower stall area (Manufacturer recommends a
minimum 2 foot clearance).
7. Heater must be installed in a wall can:
Model RM
Wall Can RMC
8.
WARNING
Risk of Fire. DO NOT install the heater in a floor,
in the ceiling, below a towel bar, behind a door,
or anywhere the air discharge may be blocked in
any manner.
9.
WARNING
Fire or Explosion May Occur. A heater has hot
and arcing or sparking parts inside. Do not use it
in areas where gasoline, paint, or flammable va
-
pors or liquids are used or stored.
10.
WARNING
Risk of Electrical Shock. Connect grounding lead
to grounding pigtail provided. Keep all foreign ob-
jects out of heater.
11.
WARNING
Risk of Fire. This heater is hot when in use.
Caution—High Temperature. Risk of Fire. Keep
electrical cords, drapery, furnishings, and other
combustibles at least 3 feet from the front of the
heater and 6 inches above and on both sides.
__________________________
Part One
__________________________
How do I install for new construction?
STEP 1
Mount The Wall Can
How do I install in an existing wall?
STEP 1
Cut A Hole In The Wall