RIVER IDROTECH 18 - 24 - 24H2O
6
3.3
SMOKE DUCT (SMOKE FITTING)
The smoke duct is the pipe that connects the appliance to the flue.
This smoke fitting must comply in particular with the following requirements:
• comply with product standard EN 1856-2;
• its cross-section must be of constant diameter and no less than that of the appliance outlet, from the firebox outlet up to the
connection in the flue;
• the horizontal section must be as short as possible and extend no more than 4 metres;
• the horizontal sections must have a minimum upward slope of 3%;
• changes of direction must have an angle no greater than 90° and be easy to inspect
• the number of changes of direction, including that for entry into the flue, and exclusion of the T in the event of a side or rear
outlet, must not exceed 3;
• it must be insulated if it passes outside the installation room
• it must not in any case cross rooms in which it is forbidden to install combustion appliances.
• the use of flexible metal and fibre cement or aluminium hoses is forbidden;
In any case, smoke ducts must be sealed against combustion products and any condensation. For this reason, it is recommended
to use pipes with silicone gaskets or similar sealing devices that withstand the operating temperatures of the appliance (e.g. T200
P1) and that by removing the gaskets, are still T400 N1 G certified.
SYSTEM TYPE
Ø80 mm PIPE
Ø100 mm PIPE
Minimum vertical length
1,5 mt
2 mt
Maximum length (with 1 union)
6,5 mt
10 mt
Maximum length (with 3 unions)
4,5 mt
8 mt
Maximum number of unions
3
3
Level section (minimum inclination 3%)
4 mt
4 mt
Installation at a height above 1200 m a.s.l.
NO
Obligatory
3.4
FLUE (CHIMNEY OR PIPED DUCT)
When creating the flue, in particular comply with the following requirements:
• comply with the applicable product standard (EN 1856, EN 1857 EN 1457, EN 1806, EN 13063..);
• be made with suitable materials to ensure resistance to normal mechanical, chemical, thermal stresses and have adequate
thermal insulation in order to limit the formation of condensate;
• have a predominantly vertical configuration and be free of choke points along its entire length;
• be correctly spaced by air gaps and isolated from combustible materials;
• the flue inside the house must still be insulated and can be inserted in an air shaft provided it complies with the regulations
for piping;
• the smoke duct must be connected to the flue by means of a Tee fitting with an inspectable collection chamber for the collec-
tion of soot and any condensate.
• where the sizing provides for wet operation, a suitable condensate collection and siphon discharge system must be set up.
We recommend checking the data plates of the flue for the safety distances that must be observed in
the presence of combustible materials and, if necessary, the type of insulating material to be used.
It is forbidden to connect the stove to a collective or shared flue with other combustion appliances or
with hood outlets.
It is forbidden to use the direct drain on the wall or towards indoor spaces and any other form of drain
not provided for by the regulation in force in the country of installation.