background image

Door/Window Sensor

Page 3

Installation Guidelines

Do not use solid core wire.

Do not use mechanical switches.

If you are connecting an external device to a door/
window sensor, do not use the built-in reed 
switches.

Do not connect fast pulse devices (such as Win-
dow Bugs) to door/window sensors.

Do not use more than 25 feet of 22-gauge, 
stranded wire in any wire run.

Do not use more than 6 feet of untwisted wire in 
any wire run.

Do not connect more than five switches, or more 
than one alarm screen to a door/window sensor.

Do not run wires parallel to electrical wires. If 
you can’t avoid a parallel wire run, keep it at least 
18 inches away from electrical wiring.

If necessary, you may cross electrical wires at a 
90 degree angle.

Programming

For complete programming instructions, refer to the 
NX-Series Receiver Modules Installation Instructions.

Testing Door/Window Sensors

Testing sensors is recommended after all program-
ming is completed and whenever a sensor-related 
problem occurs, to verify radio signal integrity and 
confirm control panel programming and response.

NOTE:

While the sensor test is a valuable tool, it only 
tests sensor operation for the current conditions. 
A sensor test should be done after any change in 
environment, equipment, or programming.

1.

Place the system in test mode.

2.

Trip the sensor by moving the magnet away from 
the sensor and listen for the correct system 
response. If the system does not respond, proceed 
to the “Troubleshooting “section.

Troubleshooting

Use the following guidelines if the system does not 
respond correctly when the sensor is activated.

Check programming and re-program sensor into 
panel if necessary.

Use an RF Sniffer (NX-468) test tool to verify 
that the sensor is transmitting. Constant beeps 
from the RF Sniffer indicate a runaway (faulty) 
sensor. Replace the sensor.

Change the position of or move the sensor to 
another location and test for correct response.

To reposition a sensor:

1.

Rotate the sensor and test for improved sensor 
communication at 90 and 180 degrees from the 
original position.

2.

If poor communication persists, relocate the sen-
sor as described below.

To relocate a sensor:

1.

Test the sensor a few inches from the original 
position.

2.

Increase the distance from the original position 
and retest until an acceptable location is found.

3.

Mount the sensor in the new location.

4.

If no location is acceptable, replace the sensor.

To replace a sensor:

1.

Test a known good sensor at the same location.

2.

If the system does not respond, avoid mounting a 
sensor at that location.

3.

If the replacement sensor functions, return the 
problem sensor for repair or replacement.

Summary of Contents for 60-639-43-EUR

Page 1: ...EUR Door Window Sensor Document Number 466 1578 NX 470 60 659 43 EUR 4 Button Keychain Touchpad Document Number 466 1478 NX 480 60 639 43 EUR Wireless Motion Sensor Document Number 466 1479 For reprin...

Page 2: ......

Page 3: ...that are likely to expose the module to moisture Avoid areas with excessive metal or electrical wiring including furnace and utility rooms Installing the Receiver Module The following steps describe...

Page 4: ...pplied from the control panel 87 21 To avoid possible equipment damage or personal injury remove power from the control panel before making any wiring connections to the module 2 Connect the module po...

Page 5: ...ions Special Settings for Door Window Transmitters Use the following guidelines when setting features 4 and 5 for door window transmitters and wireless smoke detectors Feature 4 Input Option 1 For doo...

Page 6: ...ion 7 keyfob Partition 8 keyfob Table 3 Module Programming Settings Continued Location Segment 1 Segment 2 Zone _____ Assigned to module _____ RM HE P 1 Enable sensor 2 Supervised 3 Fire supervision 4...

Page 7: ...ion 7 keyfob Partition 8 keyfob Table 3 Module Programming Settings Continued Location Segment 1 Segment 2 Zone _____ Assigned to module _____ RM HE P 1 Enable sensor 2 Supervised 3 Fire supervision 4...

Page 8: ...ion 7 keyfob Partition 8 keyfob Table 3 Module Programming Settings Continued Location Segment 1 Segment 2 Zone _____ Assigned to module _____ RM HE P 1 Enable sensor 2 Supervised 3 Fire supervision 4...

Page 9: ...put option 2 6 8 Not used Partition 1 keyfob Partition 2 keyfob Partition 3 keyfob Partition 4 keyfob Partition 5 keyfob Partition 6 keyfob Partition 7 keyfob Partition 8 keyfob Table 3 Module Program...

Page 10: ...any unwanted information in memory before any further programming 5 For new installations set the receiver zone bank Loca tion 194 to determine the starting zone number for the specific receiver modul...

Page 11: ...5 Enter the new normal supervision time 0 255 Note Choosing 0 sets the normal supervision window to 256 hours 6 Press to save any changes and automatically enter segment 2 7 Enter the new fire supervi...

Page 12: ...turn off indicate the keyfob is inactive 9 Repeat steps 4 8 to continue programming transmitter partition settings 10 Enter EXIT EXIT when finished Deleting Transmitters The following steps describe...

Page 13: ...cations not expressly approved by Interlogix Inc can void the user s authority to operate the equipment Declaration of Conformity Manufacturer s Name Interlogix Inc Manufacturer s Address 2266 North 2...

Page 14: ...tices 1420 NORTH MAIN STREET Gladewater TX 75647 800 727 2339 www interlogixinc com 2001 Interlogix Inc Interlogix is a trademark of Interlogix Inc Caddx and ITI are registered trademarks of Interlogi...

Page 15: ...have a range of 500 feet or more out in the open the environment at the installation site can have a significant effect on transmitter range Sometimes a change in sen sor location can help overcome ad...

Page 16: ...instructions refer to the NX Series Receiver Modules Installation Instructions Testing Door Window Sensors Testing sensors is recommended after all program ming is completed and whenever a sensor rela...

Page 17: ...mensions L 4 5 X W 1 2 H 94 Typical battery life 4 6 years not verified by UL Operating temperature range 10 to 120 F Notices These devices comply with part 15 of the FCC rules Operation is sub ject t...

Page 18: ...age 4 NX 450 NX 451 Door Window Sensors Caddx Controls Inc 1420 North Main Street Gladewater Texas 75647 Toll Free 1 800 727 2339 FAX 903 845 6811 Caddx is a registered trademark of Caddx Controls Inc...

Page 19: ...magnet on the other door Mount sensors with screws or brads not double sided tape Place sensors at least 5 inches above the floor to avoid damaging them Use spacers not included to keep sensors and m...

Page 20: ...r or window openings Do not use two sided tape 7 Reattach the circuit board to the sensor base 8 Reattach the sensor cover to the sensor base Connecting External Switches Door window sensors can be co...

Page 21: ...any change in environment equipment or programming 1 Place the system in test mode 2 Trip the sensor by moving the magnet away from the sensor and listen for the correct system response If the system...

Page 22: ...Operation is subject to the following two conditions This device may not cause harmful interference The device must accept any interference that may be received including interference that may cause u...

Page 23: ...Lock Button arms doors and windows Lock and Unlock Buttons when pressed simulta neously activates a panic alarm These two but tons are also used to test the sensor 60 659 Light Button arms system to...

Page 24: ...Page 2 NX 470 Keychain Caddx Controls Inc 1420 North Main Street Gladewater Texas 75647 Toll Free 1 800 727 2339 FAX 903 845 6811 Caddx is a registered trademark of Caddx Controls Inc...

Page 25: ...ng Large areas in an open floor plan downstairs family rooms and hallways are candidates for motion sensors Motion sensors are not suitable for rooms where pets can enter Use the following guidelines...

Page 26: ...the pet might reach in the detection area If the detection area contains furniture or other objects upon which the pet could climb or jump either remove these objects mount the PIR a safe distance abo...

Page 27: ...annot be used when the sensor is swivel or corner mounted Figure 5 PIR Mounting Plate Knockouts 4 Mark the location of the required holes on the mounting surface 5 Use wall anchors and screws to secur...

Page 28: ...t mode has ended an alarm can be transmitted only after 3 minutes have passed since the previous alarm This 3 minute lockout time reduces unnecessary RF transmis sions in high traffic areas thereby ex...

Page 29: ...ation and test for correct response To relocate a sensor 1 Test the sensor a few inches from the original posi tion 2 Increase the distance from the original position and retest until an acceptable lo...

Page 30: ...Page 6 NX 480 Wireless Motion Sensor Caddx Controls Inc 1420 North Main Street Gladewater Texas 75647 Toll Free 1 800 727 2339 FAX 903 845 6811 Caddx is a registered trademark of Caddx Controls Inc...

Reviews: