Chapter 2: Hardware Installation
62
SSR 8000/8600 Getting Started Guide
DC Power Supply Specifications
The following table lists the physical specifications for the SSR’s DC Power Supplies.
The following table lists the environmental specifications for the SSR’s DC Power
Supplies
DC Power Connections
•
Connect to a reliably grounded SELV source.
•
The Branch circuit overcurrent protection must be rated a maximum of 15A.
•
Use 12 AWG or 14 AWG solid copper conductors only.
•
A readily accessible disconnect device that is suitably approved and rated shall be
incorporated in the field wiring.
DC Power Supply Installation Procedure
To install a DC power supply on the SSR 8000 or SSR 8600:
1.
Ensure that the DC power supply is not powered on.
2.
If a cover plate is installed over the DC power supply slot, use a #2 Phillips-head
screwdriver to remove it. If you are replacing a power supply, unplug the power cable
from the supply you are replacing, loosen the captive screws on the power supply’s
front panel, then pull the supply out of the chassis.
3.
Slide the DC power supply all the way into the slot, firmly but gently pressing to
ensure that the pins on the back of the power supply are completely seated in the
backplane.
SSR 8000
SSR 8600
Dimensions
11.00" (L) x 7.70" (W) x 2.55" (H)
12.15" (L) x 7.70" (W) x 5.05" (H)
Weight
6.5 lbs. (2.95 kg)
12.0 lbs. (5.45 kg)
Power Output
300 W
600 W
Voltage Range
36-72V, 14 A @ 48 V nominal
36-72V, 27 A @ 48 V nominal
Operating Temperature
+5° to +40°C (41° to 104°F)
Non-operating
temperature
-30° to +73°C (-22° to 164°F)
Operating Humidity
15% to 90% (non-condensing)
Summary of Contents for SmartSwitch 8000
Page 1: ...SmartSwitch Router 8000 8600 Getting Started Guide 9032552 06...
Page 120: ...Chapter 4 Installing and Starting Cabletron CoreWatch 106 SSR 8000 8600 Getting Started Guide...
Page 124: ...Appendix A Troubleshooting 110 SSR 8000 8600 Getting Started Guide...
Page 128: ...Appendix B Technical Support 114 SSR 8000 8600 Getting Started Guide...