FIRE CONDITION
Simulate a Fire condition by connecting and activating a Call Point, or by fitting a 470 to 680
Ω
resistor across
terminals 9 & 10. The sounder output relay will operate. The ZONE 1 FIRE indicator lights and warning beeper sounds.
Press SILENCE ALARM SOUNDERS. The sounder outputs return to normal but the ZONE 1 FIRE indicator will still be lit
and the warning beeper will still sound. Press RESET/RESOUND/TEST ZONE LAMPS and the panel will go back into
alarm as the Fire condition is still present. Remove the Fire condition. Press SILENCE ALARM SOUNDERS, then
RESET/RESOUND/TEST ZONE LAMPS, and the panel reverts to normal. Repeat the test for the other zone terminals.
Notes:
1) Pressing RESET/RESOUND/TEST ZONE LAMPS when in the unsilenced Fire condition (i.e. Sounder Outputs
energised) has no effect. The sounders MUST be Silenced first before Reset is active.
2) When the Alarm Sounders are silenced, the warning beeper will sound and cannot be silenced.
3) Resetting the system from the Silenced Fire state with the fire condition still existing will retrigger the alarm.
EVACUATE
Press EVACUATE. The Sounder Outputs will operate, the ZONE FIRE indicators will light and the warning beeper
will sound. Press SILENCE ALARM SOUNDERS and the Sounder Outputs will return to the normal state. The ZONE
FIRE indicators will still be lit and the warning beeper will still be active. Press RESET/RESOUND/TEST ZONE LAMPS
to return the panel to normal state.
TESTING THE SYSTEM
Check each detector and sounder on the system, and check the functions of the panel. Check all circuits for open
and short circuit faults. If continuity diodes are fitted remove each head in turn and check that call points are still
operative. When testing is complete return the keyswitch to NORMAL position.
ANCILLARY FACILITIES
(Links and internal features are shown in Fig 6 below)
ENGINEERS TEST (NON-LATCH TEST) FACILITY
This range of panels has a non-latching test facility
which allows manual call points and smoke detectors
to be tested and reset automatically. To set this facility
move the link marked ‘PL1’ on the main PCB from the
lower to the upper position and the adjacent
indicator will light, the warning beeper will sound
and cannot be silenced. When an alarm condition is
caused the alarm sounders will operate for about half
a second and will silence for three seconds before
resounding. This will continue until the cause of the
alarm is removed by the smoke clearing from a
detector or the call point being reset. When testing is
complete, replace the link to the lower position.
ZONE ISOLATION FACILITY
Each Detector Zone can be isolated individually by moving the links (PL2/PL4/PL5/PL6) from the lower to the upper
position. The adjacent indicator and relevant ZONE FAULT indicator will light to show that the zone is isolated. The
warning buzzer will sound and cannot be silenced. When testing is complete, replace the link to the lower position.
TO REVERT TO SHORT CIRCUIT = FIRE
This facility overrides the short circuit fault monitoring for each zone and allows the panel to be used on
installations which do not have Call Point Resistors fitted. It produces a short circuit Fire condition when activated.
To enable this facility cut the wire links (LK1/LK2/LK3/LK4) on the main PCB.
AUXILIARY EXPANSION PLUG (PL10)
This plug connector offers facilities for driving Repeater Panels, Fire and Fault relays and a "Class Change" input.
These facilities require various ancillary devices to be added to the panel (not included).
AUX 24V +VE
This output is a regulated, unmonitored, output fused at 1A (F4), available from terminal 1 in the panel’s base
connections. With link ‘PL3’ on the main PCB linked in position furthest from the F4 fuse this output is continuous.
If linked nearest to the F4 fuse then the output is present when the panel is normal but is switched off when the
relay is activated. This facility can be used to provide a fail-safe output via AUX 24V, that "switches off" when the
sounders are activated, or if power to the panel fails.
Note
: Any load provided by this output increases the quiescent drain on the panel’s supply which in turn affects
the stand-by time of the system. It is not intended to supply door release systems.
VOLTAGE FREE RELAY CONTACTS
These single pole relay outputs, available via terminals 2 (normally closed), 3 (common), and 4 (normally open) in
the panel’s base connections, change over when the sounders are activated. They must not be used to switch
Mains potentials, the contacts being rated at 30Vdc and 1.0A.
PL9
PL13
Zone
Expansion
Auxiliary Expansion
PL10
Keyswitch
Connector
PL11
DO NOT
ADJUST
VR1
Fig 6
F1
PL3
F4
AUX 24V
Output Fuse
Battery Fuse
PL7
RED
F3
F2
Sounder
Circuit Fuses
Cut links for
short circuit = fire condition
PL2
PL1
PL4
PL8
PL6
not used
PL5
Primary Loom
Connector
FIRE ALARM
ancillaries
3 of 4
Approved Document No. DFU0384011 Rev 2 Draft 4