C-TEC CAST CA738 Installer'S Manual Download Page 2

CONN1 (SNDR + -) Connector - See Fig.1
Connection to ActiV sounders and ActiV sounder 
VADs.
Fit the supplied 27K EOL across the terminals of 
the last device on the circuit.
All terminals can accept cables up to 1.5mmØ.

This product must be installed and tested in accordance with applicable local and/or national 
regulations.
The I/O module is designed for indoor use only and may be flush or surface mounted in a place
where the status of the LED indicators are clearly visible.
Two mounting holes are provided on the I/O module for fixing to a standard UK double-gang
back box with minimum 35 mm depth. DO NOT OVERTIGHTEN THE FIXING SCREWS.

CONN2

CONN1

Loop

L1+ L2+

CAST Loop

(to / from fire panel)

L1+

L2+

-

-

SNDR

CA738 

Sounder Controller

Refer to the individual 

instructions supplied with 

each ActiV device for 

wiring and specifications.

Connect EOL in last

device on sounder circuit.

27K EOL

S

+Ve

-Ve

ActiV Sounder

+Ve

-Ve

ActiV

Sounder VAD

S

All wiring must be installed in accordance with all applicable national, regional or local standards. 
In the UK this is BS 7671 (IET Wiring Regulations).

Wiring and Connections

E&OE. No responsibility can be accepted by the manufacturer or distributors of these devices for any misinterpretation of 
this instruction, or for the compliance of the system as a whole. The manufacturers policy is one of continuous improvement 
and we reserve the right to make changes to product specifications at our discretion and without prior notice.

Manufacturer: Computionics Limited (C-TEC), Challenge Way, Martland Park, Wigan, Lancashire WN5 0LD. 

www.c-tec.com

Approved Document No. DFU0007380 Rev 1

Installation and Testing

Terminal

Function

L1+

+Ve

L2+

+Ve

-Ve

-Ve

CONN2 Loop Connector
CAST loop connection to / from CIE.

CAST Range

2 of 2

Fig.1: CA738 Wiring & Connections