Basic programming 

Parameter 
Name 

Default 
Value 

0

 

1

 

2

 

3

 

UHS5 Handset Graphics 

Description 

 

 

Button Activation 

 

 

On 

 

On 

 

 

 

 

Turn lights on. 

Off  

 

Off 

 

 

 

 

Turn lights off. 

Walk test 

Off 

On 

Off 

 

 

 

When set to On this causes a red LED to flash on 
the sensor when it detects movement. Use this 
feature to check for adequate sensitivity levels. 

Time Out 

(Time 
adjustment) 

20 mins 

1, 10 & 
20 
minutes 

5, 15 & 
30 
minutes 

10 
seconds 

 

 

Once the detector is turned on, this value sets 
how long the lights will stay on once movement 
has ceased. 

Lux on 
level 

(Switch 
level on) 

2, 5 & 7 

4, 6 & 9 

 

 

 

Lux level setting to prevent the luminaires being 
switched on if the ambient light level is sufficient 
(adjustable between 1 and 9). The luminaires will 
always be switched on at level 9.  

Lux off 
level 

(Switch 
level off) 

2, 5 & 7 

4, 6 & 9 

 

 

 

Lux level setting to switch the luminaires off during 
occupancy if the ambient light level goes above 
the setting (adjustable between 1 and 9). Level 9 
will always keep the lights on. This setting can be 
used for “window row switching”. 

Note: the Lux Off Level value must always be 
greater than the Lux On Level value. 

Sensitivity 

1, 5 & 9 

3, 6 & 8 

 

 

 

Sensitivity level for detecting movement. 
1 = low sensitivity 
9 = high sensitivity 

Defaults 

 

 

 

 

 

Returns the unit to the default settings. 

Presence / 
Absence 

Presence  Presence  Absence   

 

 

Presence mode allows the output to turn on when 
movement is detected and off when movement 
ceases. Absence mode allows the output to turn 
off when movement ceases, but must be manually 
turned on first. 

Shift 

 

 

 

 

 

 

Use this button to select the settings in red and 
blue signified by the ‘Shift 1’ and ‘Shift 2’ LEDs 

Number of Shift key presses 

The functionality of the EBDSPIR-PRM is controlled by a number of parameters which can 
be changed or programmed by any of the following devices: 

 

UHS5

 Infrared Handset. See below for programmable functions. 

 

UNLCDHS 

Infrared Handset (with LCD). See user guide for full programming details. 

For most basic programming operations the UHS5 handset can be used and the following procedures 
are based on using this device. 
Point the handset at the Sensor and send the required programming commands to the unit as shown 
below. 
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses. 

Note: other functions on the UHS5 which are not shown below are not applicable to this product.

 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

What if the load does not turn ON? 

 

Check that the live supply to the circuit is good.  

 

Check that the load is functioning by bypassing the sensor (e.g. link terminals 

L

 and 

L/ Out

 on Channel1). 

 

If the detection range is smaller than expected, check the diagram on page 2. Rotating the sensor slightly may 
improve the detection range.  

HINT: 

The Walk Test LED function can be used to check that the unit is detecting movement in the required area. 

What if the load does not turn OFF? 

 

Ensure that the area is left unoccupied for longer than the Time Out Period. 

 

Ensure that the sensor is not adjacent to circulating air, heaters or lamps. 

Fault finding 

Summary of Contents for EBDSPIR-PRM

Page 1: ...ck features Ceiling PIR presence absence detector EBDSPIR PRM EBDSPIR PRM IP Product Guide PIR Sensor Detects movement within the unit s detection range allowing load control in response to changes in...

Page 2: ...ce The load is manually switched on When the area is no longer occupied the load will automatically switch off after the adjustable time period has elapsed In either case sensitivity to movement of th...

Page 3: ...e mode has been selected Note the above adjustments can also be made using the UHS5 or UNLCDHS handsets See Programming sections When power is applied to the unit the load will turn on immediately Set...

Page 4: ...read back the device will flash its LED and the value will be shown against the parameter in the menu To read back all of the parameters in a menu Press and hold the R Read button for more than 1 sec...

Page 5: ...put to turn off when movement ceases but must be manually turned on first Shift Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Number of Shift key pre...

Page 6: ...to be implemented with a lux off level set When the button is pressed the lights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off again aft...

Page 7: ...7 This page intentionally left blank...

Page 8: ...uency 50Hz Maximum Load 10A of lighting and or ventilation including incandescent fluorescent compact fluorescent low voltage by switching the primary of transformer Power consumption On 875mW Off 895...

Reviews: