Document:
Date
Created By:
LPN00710X0001A0_A
3-17-2023
TMT
INSTALLATION INSTRUCTIONS
C-WP-E-TR Series
http://lighting.cree.com/warranty | 1-800-236-6800
CAUTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety
precautions should always be followed including the
following:
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1. DANGER
- Risk of shock- Disconnect power before
installation.
DANGER
– Risque de choc – Couper l’alimentation
avant l’installation.
2. This Product Must Be Installed In Accordance With The
Applicable Installation Code By A Person Familiar With
The Construction And Operation Of The Product And The
Hazards Involved.
Ce Produit Doit Être Installé Selon Le Code D’installation
Pertinent, Par Une Personne Qui Connaît Bien Le
Produit Et Son Fonctionnement Ainsi Que Les Risques
Inhérents.
3. Suitable for wet locations.
Convient aux emplacements mouilles.
4. Wall mount only.
Installation murale seulement
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
MOUNTING OVER RECESSED JUNCTION BOX
NOTE:
Knockouts are provided for mounting over 3" octagonal or 4"
octagonal boxes.
1. Remove lens assembly by loosening screws on side of frame.
Swing lens assembly open,disconnect quick connect wiring
connector(s) and lift lens assembly upward to remove from housing.
2. Drill out appropriate knockouts in back box for attachment to junction
box. Also drill knockout for wiring access.
NOTE:
Fixture should not be exclusively supported by junction
box. Drill additional knockouts toward corners of fixture to provide
additional support. Do NOT drill within 1/4" (64 mm) from edges of
fixture.
3. Pull supply leads from junction box through wall of back box. Attach
back box to mounting surface using hardware (supplied by others)
appropriate for mounting surface.
NOTE:
A high grade caulking material such as silicone rubber,
should be used around perimeter of back box to prevent water
leakage into fixture or junction box.
4. Position switches to select desired CCT and wattage. See
Figure 1.
NOTE:
Factory setting for wattage is highest setting. Factory setting
for CCT is 4000K.
NOTE:
If 0-10V dimming is to be used, switch setting for wattage
must be 100%.
5. Make wiring connections per the
Electrical Connections
section.
6. Replace the lens assembly on hinges, re-connect quick-connect
wiring connectors, and swing lens into place. Re-tighten screws that
were loosened in Step 1.
1. Remove lens assembly by loosening screws on side of frame.
Swing lens assembly open,disconnect quick connect wiring
connector(s) and lift lens assembly upward to remove from housing.
2. Drill holes in four corners of back box to allow for attachment of
back box to mounting surface. Do NOT drill within 1/4" (64 mm)
from edges of fixture.
3. Attach back box to mounting surface using hardware (supplied by
others) appropriate for mounting surface.
NOTE:
A high grade caulking material such as silicone rubber,
should be used around perimeter of back box to prevent water entry.
4. Remove appropriate threaded plugs on sides of fixture and route
electrical conduit to the holes desired. Feed the supply leads through
the conduit and into the back box.
NOTE:
Use of teflon tape on the conduit threads will ensure a
watertight seal.
5. Position switches to select desired CCT and wattage. See
Figure 1.
NOTE:
Factory setting for wattage is highest setting. Factory setting
for CCT is 4000K.
NOTE:
If 0-10V dimming is to be used, switch setting for wattage
must be 100%.
6. Make wiring connections per the
Electrical Connections
section.
7. Replace the lens assembly on hinges, re-connect quick-connect
wiring connectors, and swing lens into place. Re-tighten screws that
were loosened in Step 1.
WALL MOUNTED WITH CONDUIT FEED
6L
9L, 12L AND
18L
FIGURE 1
23L