Page 17
21
Cell_OV3
The cell voltage is too high.
Contact the Technical
Support.
22
Charge_OT1
The cell temperature is too high.
Normal alarm, no further
action required
23
Charge_OT2
The cell temperature is too high.
Normal alarm, no further
action required
24
Charge_OT3
The cell temperature is too high.
Normal alarm, no further
action required
25
Charge_UT1
The cell temperature is too low.
Normal alarm, no further
action required
26
Charge_UT2
The cell temperature is too low.
Normal alarm, no further
action required
27
Cell_OT
The cell temperature is too high.
Contact the Technical
Support.
28
SeqStartTimeout
Internal fault of battery system.
Contact the Technical
Support.
29
Battery Diff
Internal fault of battery system.
Contact the Technical
Support.
30
BCUStart
Restart
If it occurs frequently,
please contact the
Technical Support.
31
BatteryLock
The cell voltage is too low.
Contact the Technical
Support.
32
ZeroResetErr
Internal fault of battery system.
Contact the Technical
Support.
33
ZeroResetFault
Internal fault of battery system.
Contact the Technical
Support.
34
BIC_AddrCalc
Battery address matching
Normal alarm, no further
action required
35
ChargeFault
Internal fault of battery system.
Contact the Technical
Support.
36
DischargeFault
Internal fault of battery system.
Contact the Technical
Support.
37
BatteryBreak
Internal fault of battery system.
Contact the Technical
Support.
38
HardwareFault
Internal fault of battery system.
Contact the Technical
Support.
39
PrechargeFault
Internal fault of battery system.
Contact the Technical
Support.
40
DCBusFault
DC Bus short connected
Contact the Technical
Support.
41
UpdateSuccess
Update succeed
Normal alarm, no further
action required
42
UpdateFail
Update fail
Contact the Technical
Support
43
SystemRestart
System restart
Normal alarm, no further
action required