The following table describes situations that may seem abnormal although no error code is displayed on the 
machine. For any other problems, please contact the seller. 

 

Problem 

Possibles causes 

Possible solutions 

The heat pump will 
not 
start 
 

No power supply 
 

Check that no circuit breakers are 
tripped 
Check that the electrical connections 
are not loose. 

The machine is off 

Press the On/ Off button. 

The temperature set point 
has 
been over shot 

Check the set point temperature, 
compare this with the water temperature at the 
inlet. 

The heat pump is 
running, but the pool 
water temperature is 
not changing 
 

Heat loss is too high 
 

Make sure that the pool is covered with 
an isothermal cover while it is not in 
use. 
Make sure that pipes connecting the 
heat pump to the pool are buried at the 
correct depth, or are correctly lagged. 
In the case of above-ground pools, 
check that the heat loss from the pool 
walls is not too high. 

The daily run time is too 
short 
given the coolness of 
ambient air 
 

Inadequate programming of the timer 
that controls filtration start and stop: 
- Length of the filtration cycel too short 
- Filtration only at night when the 
ambient T°C is particularly low 

The ambient air 
temperature is 
exceptionally low 

Wait until the temperature returns to 
normal levels. 
Check that the machine is correctly 
sized for the water volume and period 
of use. 

Air is not circulating freely 
 

Check that the evaporator fins are 
clean. 
Check that the installation instructions 
set out in paragraph IV.1 have been 
respected 

The heat pump trips 
the 
magnetic thermal 
circuit 
breaker is an 
untimely 
manner 
 

Circuit  breaker  incorrectly 
set 

Check that it is set in accordance with 
recommendations set out in paragraph 
IV.3 

Electrical short circuit 
 

Have the heat pump electrical wiring 
and its power supply checked by a 
qualified electrician. 

Circuit breaker common to 
several devices and under 
sized 
 

Install a circuit breaker specific to 
the hat pump in accordance with the 
recommendations set out in paragraph 
IV.3 

The heat pump trips 
the RCD  

Earth leakage current 

Have the heat pump electrical wiring 
and its power supply checked by a 
qualified electrician. 

Summary of Contents for Fairland IPHCR100T

Page 1: ...1 18 2018 12 B Code 33315 BWT FAIRLAND INVERTER PLUS Pompe chaleur IPHCR15 IPHCR20 IPHCR26 IPHCR33 IPHCR40 IPHCR45 IPHCR55 IPHCR70 IPHCR70T IPHCR100T...

Page 2: ...nsions 24 V Product installation 25 V 1 Siting 25 V 2 Support 26 V 3 Handling 26 V 4 Connection to the hydraulic circuit 26 V 5 Wiring 27 V 6 Heating priority 28 VI Start up and operation 28 VII Upkee...

Page 3: ...d after installation 1 Use a It must be installed or removed by professionals and it is forbidden to dismantle and refit without permission b Don t put obstacles before the air inlet and outlet of the...

Page 4: ...far away from any source of fire d Storage place must be bright wide open and good ventilation ventilation equipment is required 4 Maintenance Notice a If maintenance or scrap is required contact a qu...

Page 5: ...s cheaper than other conventional heating means Unlike On Off heat pumps Inverter heat pumps can modulate their operating mode and adapt it to the swimming pool s heating demand This characteristic ma...

Page 6: ...3 68 90 93 120 Dim length x width x height mm 894 x 359 x 648 954 x 359 x 648 954x429 x 648 954x429 x 755 1084 x 429 x 948 1154 x 539 x 948 Sound power level dB A at max middle min speeds 61 53 9 51 6...

Page 7: ...he machine will revert to normal operating mode The heat pump is fitted with a flow controller that only allows the machine to start up when the water flow rate through the machine is adequate see the...

Page 8: ...reated against corrosion Piping must be attached to the wall to be supported but not by the machine Make sure the filtration pump can overcome the height difference between the filtration pump and the...

Page 9: ...A max bipolar trtrapolar Power cable wire cross section in mm2 3 x 1 5 3 x 1 5 3 x 2 5 3 x 2 5 3 x 2 5 3 x 2 5 3 x 4 0 3 x 6 0 5 x 2 5 5 x 2 5 Remote installed control panel cable wire cross section i...

Page 10: ...nds to access the parameter modification menu The P0 parameter followed by 0 is displayed on the screen P0 0 Press to modify P0 then press to scroll until 1 is displayed P0 1 Press once again to confi...

Page 11: ...it shuts off still lit VI 2 Selecting the operating function There are three operating functions available heating cooling auto If the auto function is active the machine will automatically go into he...

Page 12: ...timately selected by the operator will be active when restarting the heat pump after being off VI 3 Selecting the set temperature value Screen being unlocked press or to display the set temperature an...

Page 13: ...he caps provided to avoid any unwanted guests taking up residence over the winter period Cover the machine if possible to prevent dirt from building up on the external parts VII 2 Technical inspection...

Page 14: ...at cooling mode 7 P0 Controller communication failure 8 P1 Water inlet temp sensor failure 9 P2 Water outlet temp sensor failure 10 P3 Gas exhaust temp sensor failure 11 P4 Evaporator coil pipe temp s...

Page 15: ...coolness of ambient air Inadequate programming of the timer that controls filtration start and stop Length of the filtration cycel too short Filtration only at night when the ambient T C is particula...

Page 16: ...16 18 2018 12 B Code 33315 NOTES...

Page 17: ...17 18 2018 12 B Code 33315...

Page 18: ...18 18 2018 12 B Code 33315 Version B18Ir32...

Reviews: