I N S T AL L AT I O N   AN D   M AI N T E N AN C E   M AN U AL   V A L V E   R E G U L AT E D   L E AD   AC I D   B AT T E R Y  

 

2 | P a g e  

 

The best operating condition for float charge 
battery is always in fully charged state. Under 
this condition, battery will obtain its longest 
lifespan. When operating in float charge 
condition, make sure each monobloc is 
charged with a constant voltage of 
2.20÷2.30Vpc. If the float charge voltage 
exceeds this level, it will reduce the battery 
capacity and operational service life. When 
the ambient temperature is in the range 20 to 
30ºC, the voltage can be adjusted with 
gradient rate -3mV/ºC. We recommend the use 
of constant-voltage chargers featuring 
automatic voltage adjustment in accordance 
with temperature. 
(2) Cyclic 

operation 

Charging parameters for cyclic operation are 
listed below: 

Charging voltage: 2.4Vpc (25°C) 

Initial limited charging value: I = 0.05C

10

 ~ 

0.3C

10

 

Gradient: -5mV/°C 

Whether charge process is over can be judged 
according to any of the following two 
situations: 
Generally, the charge process lasts 18 to 24 
hours. However the charging time may by 
shortened when the previous discharge is not 
deep. For example: the charging time can be 
shortened to 10 hour after 20% discharge. 
During the final stage of constant charge, the 
charging current remains constant for three 
hours. 
In discharge process, make sure the terminal 
voltage is higher than the terminating voltage 
(protection point), and the battery should be 
charged as soon as the discharge process is 
over. 

2. 

C ha r gi n g  

There are 2 battery charge modes: float 
charge and equalize charge. In charge 
process, the charged capacity must be 1. 07 
times  of  pre v ious  dis charged c apac it y 

(1) 

Float charge 

Constant voltage: 2.20÷2.30Vpc (25°C), 

gradient: -3mV/°C. 

Initial limited charging value: I = 0.05C

10

 ~ 

0.3C

10

 

(2) 

Equalize charge 

Constant voltage: 2.40÷2.45Vpc  (25°C), 

gradient: -5mV/°C. 

Initial limited charging value: I = 0.05C

10

 ~ 

0.3C

10

 Equalize charge voltage is slightly 

higher than float charge voltage, which can 
shorten the charging time. 

Equalize charge may be adopted in case of 
any one of the following situations: 

Discharge more than 20% of rated 

capacity 

Storage period longer than three months 

Continous float charge for three to six 

months 

Voltage imbalance between cells is big in 

float charge 

(3) 

Recharge after storage 

The battery is fully charged at factory 
delivery. However, when the battery is stored 
for a period of time, capacity loss may occur. 
In this case, battery should be re-charged 
before installation, with equalize charge mode 
recommended. After re-charging, the battery 
should be installed and put into use as soon 
as possible. 

 

3. 

Ma in tena nc e and  cauti ons  

(1) 

When the battery is operating, the 

following data should be measured and 
recorded monthly: 

Float voltage of each cell and monobloc 

Float current 

Total battery voltage 

Ambient temperature 

Date of measuring 

(2) 

Check the connectors yearly for 

looseness, corrosion and dirt. The loose 
connector should be tightened, and the dirty 
or corrosive connectors should be cleaned 
immediately. 
(3) 

Check the battery cases for leakage 

and distortion, if there is any acid leakage 
around the posts or safety valve, or the 
temperature is unusual, find out and solve the 
problem, or replace the battery. 
(4) 

Never install battery inside sealed 

containers. 
(5) 

Battery should be charged as soon as 

the discharge process is over

 