5 | Installation
20 / 36
0870206364_WV1200-2400A_Ex_-0004_IM_en
5.7.1 Wiring Diagram Resistance Thermometer
Part no.:
0651 536 445 (without transmitter)
Supplier reference:
PT100: Albert Balzer AG
ref. TFE-B D A B
Maintenance procedure:
P&ID position:
TSA+/0101 “exhaust gas temp.”
Wiring without transmitter:
1
2
3
4
1 and 2 = Red ; 3 and 4 = White
Electrical data:
U
i
= 30 VDC ; I
i
= 100 mA ; P
i
= 750 mW ; L
i
= 0.015 mH ; C
i
= 280 pF
Warning signal:
a warning signal can be set prior the trip signal.
Trip signal:
T3 (i) / T4 (o)
T
trip
(TSA+/0101) = 150°C (for WV 1200 and 1800 A)
T
trip
(TSA+/0101) = 160°C (for WV 2400 A)
Trip signal:
T4 (i) / T4 (o) (specific conditions only)
T
trip
(TSA+/0101) = 125°C (for WV 1200, 1800 and 2400 A)
Part no.:
0651 536 447 (with transmitter)
Supplier reference:
PT100: Albert Balzer AG
ref. TFE-B D A B
Transmitter: Hauser
ref. TMT 187-B41FIA
Maintenance procedure:
P&ID position:
TSA+/0101 “exhaust gas temp.”
Wiring with transmitter:
2
1
+
-
1
2
3
4
5
6
+
-
1 = Brown ; 2 = Blue
Electrical data:
U
i
= 30 VDC ; I
i
= 100 mA ; P
i
= 760 mW ; L
i
= 0 µH ; C
i
= 0 pF
4 ... 20 mA
►
0 ... 250 °C
Warning signal:
a warning signal can be set prior the trip signal.
Trip signal:
T3 (i) / T4 (o)
T
trip
(TSA+/0101) = 150°C
►
13.6 mA (for WV 1200 and 1800 A)
T
trip
(TSA+/0101) = 160°C
►
14.24 mA (for WV 2400 A)
Trip signal:
T4 (i) / T4 (o) (specific conditions only)
T
trip
(TSA+/0101) = 125°C
►
12 mA (for WV 1200, 1800 and 2400 A)