Installation
IMPORTANT -
Electrical connections must be
carried out by a suitably qualified person and in
accordance with all relevant local building and
installation regulations.
Electrical connections
1. This appliance is designed to be connected to
an earthed electrical mains supply.
2. The appliance must be connected to a double
pole switched Fuse Connection Unit (FCU) with
a minimum rating of 32 A and a minimum
contact clearance of 3mm in accordance with
IEE regulations.
3. Make sure the switched FCU is located adjacent
to the appliance within a maximum distance of
2m. The switched FCU must not be located
above the appliance but should be easily
accessible in case of an emergency.
4. The switched FCU must be connected to the
mains consumer unit using a single spur. Do not
connect the switched FCU to the lighting or
socket spurs.
5. Connections should be made via an electrical
cable of H05V V-F specification or better.
6. Sufficient electrical cable should be used to
allow the appliance to be withdrawn from the
wall.
7. Make sure all electrical cabling is routed to
prevent trapping..
8. Make sure the electrical cable is not in contact
with any hot parts of the appliance once it is in
position to avoid danger of melting and
electrical short circuit.
9. The terminal box on the rear of the appliance
can be accessed by removing the cover using
suitable tools.
10. Connect one end of the electrical cable to the
terminals on the rear of the appliance following
the connection diagram shown in figure 3.
11. Connect the remaining end of the electrical
cable to the switched FCU following the
connection diagram shown in figure 4.
Positioning & electrical connection
Customer Helpline
0845 600 4632
Figure 3
Figure 4