Custom Parametrisation | 6
0870208958_INVEOR_VFD_-0002_PCI_en
13 / 44
6
Custom Parametrisation
DANGER
Maintenance work without disconnecting the variable-frequency drive.
Risk of electrical shock.
• Disconnect and isolate the variable-frequency drive before attempting any work on it.
High voltages are present at the terminals and within the variable-frequency drive for
up to 10 minutes after disconnection of the electrical supply.
• Always ensure by using a suitable multimeter that no voltage is present on any drive
power terminals prior to commencing any work.
DANGER
Carry out any work on the variable-frequency drive and motor.
Risk of electrical shock!
• Electrical installation work must only be executed by qualified personnel.
NOTICE
Change factory settings.
Risk of damage to the machine!
If wrong or not allowed parameters have been set, Busch disclaims any liability for dam-
age to the machine.
• Change only the allowed parameters described in the chapter
.
NOTE
Parameterisation is possible prior to device installation.
Parameterisation can be performed before the drive controller is installed in the motor.
The variable-frequency drive has a 24 V low-voltage input for this purpose, which can
supply the electric system without requiring mains power.