The following terms are used throughout this manual to bring attention to the presence of hazards of various risk 
levels.

WARNING

Indicates a potentially hazardous situation which, 

if not avoided, could result in death, serious injury 

or substantial property damage.

CAUTION

Indicates a potentially hazardous situation which, 

if  not  avoided,  may  result  in  moderate  or  minor 

injury or property damage.

Basic Operation

A.

 

General

. This water boiler is equipped with controls 

for proper operation. All controls must be in proper 

working order. Contact a qualified service agency to 

provide annual maintenance as specified in Installation, 

Operating and Service Instructions.

1.  Limit.

 See Figure 1. A device which automatically 

interrupts boiler operation when the water 
temperature exceeds the set point. Maximum 
allowable temperature is 220°F.

 

Original equipment with this boiler is U.S. Boiler 

IQ Control and Limit Rated Sensor combination. 

The IQ Control shuts off boiler main burners when 

boiler water temperature exceeds pre-programmed 

IQ control water temperature set point.  Boiler main 

burners will re-light automatically, providing the call 

for heat is present, when boiler water temperature 

falls below pre-programmed control water 
temperature set point less the set point differential.

2.  Flame Rollout Switch.

 See Figure 1. A device 

which automatically interrupts boiler operation 

when flames or excessive heat are present in the 

combustion area enclosure. The control is a single 

use device.  The control is located in the combustion 

area enclosure.   If the control was activated to 

interrupt boiler operation, do not attempt to place 

boiler in operation. Contact a qualified service 

agency.

WARNING

Service on this boiler should be undertaken only 

by trained and skilled personnel from a qualified 

service agency.

WARNING

Do  not  reset  Blocked  Vent  Switch  unless  a 

qualified  service  agency  has  determined  and 

corrected the cause of any blockage in the vent 

system or chimney.

3.  Blocked Vent Switch

  See Figure 1.  A device 

which automatically interrupts boiler operation 

when  excessive vent system blockage occurs.  If the 

control was activated to interrupt boiler operation, 

do not attempt to place boiler in operation.  Contact 

a qualified service agency.

4.  Electronic Ignition System

 - see Figure 1. The 

Electronic Ignition (EI) System consists of:

a.  a solid state ignition control with integral 

ignition module to initiate, monitor and stop 

burner operation.

b.  a combination gas valve to regulate gas flow to 

the main burners.

c.  a pilot burner to provide the ignition source for 

the main burners.

 

B.

 

Instructions

 to place the boiler in operation and to turn 

off the boiler are shown on the Operating Instruction 

Label posted on the left jacket panel of the boiler. The 

Operating Instruction Label is shown in Figure 2.

C.

 

The Sequence of Operation

 is shown in Figure 3.

CAUTION

Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical 

supply to the pump. Instead, shut off the gas supply at a location external to the appliance.

En cas de surchauffe ou si I'admission de gaz ne peut étre coupée, ne pas couper ni débrancher 

l'alimentation électrique de la pompe.  Fermer plutôt le robinet d'admission de gaz à l'extérieur de I'appareil.
Do not use this boiler if any part has been under water. Immediately call a qualified service technician to 

inspect the boiler and to replace any part of the control system and any gas control which has been under 

water.