Installation / Service / User Manual
BURNERTECH
16
5.1.3
Fan speed
Unless prior knowledge of the application is available or alternative speeds are requested, each
burner is pre-programmed with the following fan speeds:
INVERTERJET
50
90
Maximum
5850 rpm
8500 rpm
Minimum
1500 rpm
1500 rpm
Ignition
30%
5.1.3.1 Fan speed adjustment
The following flowchart (Fan speed control flowchart) shows how the fan speed is controlled during
a complete burner sequence. The basic states are:
•
Stand-by, fan is off or at Continuous Fan speed when this option is selected;
•
Pre-purge;
•
Ignition;
•
Run state, fan speed is controlled by modulation input
, see section “Normal heating mode”.
•
Post purge.
The desired fan speed in Continuous and Ignition mode can be independently programmed.