The Contractors Choice
thermOweld
®
+1 (918) 627-5210 • 1-800-558-1373 • WWW.THERMOWELD.COM
ELECTRICAL GROUNDING • CATHODIC PROTECTION • ELECTRIC UTILITY • RAIL
Tel. +1.800.558.1373
Tel. +1.918.627.5210
www.thermoweld.com
INSTRUCTIONS FOR THERMOWELD GROUNDING CONNECTIONS - CABLE TO GROUND PLATE
CR-27
Place end of cable un-
der the center of the tap
hole. With mold closed,
insert ground plate. If using
38-4178-00 ground plate and
500 MCM or larger cable, gap cable
and end of ground plate 1/8" under
center of tap hole.
CR-31
Place end cable under center of tap hole. With mold
closed, insert ground plate. Type CR-31 is welded in an
inverted position and the resulting riser is used to place
the ground plate on top of 1/2" pipe. This helps position
the ground plate flush with a floor slab.
CR-32
Place cable in mold. With mold closed, insert ground
plate. Type CR-32 is welded in an inverted position and
the resulting riser is used to place the ground plate on top
of 1/2" pipe. This helps position the ground plate flush
with a floor slab.
CR-30
Place cable in the mold. With mold
closed, insert ground plate.
CR-29
Place end of cable under center of
tap hole. With mold closed, insert
ground plate.
ECN 2552 REV "F" 03/05/13 34-5381-15