background image

Page 16 of 20 

15.

 

Gas rating of Burley Flueless Appliances 

 

Burley’s  Flueless  Gas  Appliances  are  all  gas  input  rated  in  the  factory  and  undergo  further  line tests  for 
combustion, sooting and visual performance. For Installers who wish to gas input rate appliances we need 
to establish tolerances for pass and fail. 

Manufacturers Tolerances 

The Heat Input on appliances can be expressed as either a Nett or a Gross figure. When the installer is gas 
rating from the meter they will be using gross heat input which is 10% higher than Nett. This conversion 
has to be taken into account if the manufacturer has quoted a nett figure. 
The  manufacturer  also  has  to  account  for  production  tolerances  on  pipes,  injectors,  valves  etc  and  is 
allowed a f/-5% tolerance on the maximum rate. 

Burn Down 

Cold appliances generally allow a greater rate of gas to pass through them and once the appliance warms 
the gas density alters and causes the rate to reduce to the figure stated. This is known as Burn Down. 
Manufacturers carrying out their technical tests allow appliances to be fully warm and burn down before 
taking readings and this is typically after 1 hour. Some appliance manufacturers quote a ‘cold’ figure for 
the gas rate so that installers can measure this immediately.  

Installer Tolerances 

It is important to take a gas rate test over a reasonable period of time so that the capacity of the meter is 
used.  On  low  Input  appliances  such  as  our  flueless  this  is  even  more  critical  because  uncertainties  can 
creep in. It is worth measuring over a 5 minute period to make sure. 
It is also important to get your inlet pressure to 20mBar. 
In a gas appliance factory compensation is also made for variations in  

 

% Saturation of Gas 

 

Variation in Calorific Value 

 

Variation in Gas Density 

 

Gas Temperature 

 

Gas Pressure 

 

Atmospheric Pressure 

 

Meter Calibration 

 

Stopwatch Calibration. 

In the home it is not possible to correct for these therefore an uncertainty factor needs to be built into all 
measurements.  
Currently Gas Safe™ (formerly CORGI) does not quote a figure on this uncertainty but the measured gas 
rate could vary by +/-5%. 

Conclusion 

In adding all the variables together,  

 

an appliance quoting Gross Heat Input could be anything from +/-10% of the quoted heat input 

 

an  appliance  quoting  Nett  Heat  Input  could  be  anything  from  0%  to  +20%  of  the  quoted  figure 
when measured as a Gross figure. 

 

If the appliance is cold anything up to a further 10% error could be expected and we don’t quote 
these figures because they change rapidly. The figures shown below are hot figures. 

 

 

Heat Input  

Minimum 
(Gross) 

Max (Gross) 

Cu Ft / Hr 

Cu M / Hr 

Environ, Esteem, 
Latitude 

2.5kW Nett 

2.5kW Gross 

3.0kW Gross 

8.49 

0.2404 

Ambience 4121 

3.5kW Nett 

3.5kW Gross 

4.2kW Gross 

11.67 

0.3304 

Acumen / Elan 
4111 

4.2kW Nett 

4.2kW Gross 

5.3kW Gross 

14.85 

0.4205 

Longitude 

4.2kW Nett 

4.29kW Gross 

5.3kW Gross 

14.85 

0.4205 

Summary of Contents for LONGITUDE

Page 1: ...Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Telephone 44 0 1572 756956 Fax 44 0 1572 724390 e mail info burley co uk web www burley co uk G4530 39InstUser G20 G31 March 2019 TO OBTAIN...

Page 2: ...valve Elbow 82 340 Elbow 92 160 Pilot SIT 9116 Seagas P451 Average measured NO2 room 119ppb 115 1ppb The inlet pressure must be within 1mBar of specification with all gas appliances in the house switc...

Page 3: ...o convert cubic feet ft to cubic metre m divide the room volume in cubic feet by 35 3 3 6 The heater must not be installed in high rise blocks of flats unless a gas supply already exists bed sitting r...

Page 4: ...connect the gas supply to the 8mm elbow on the fire Leak test the supply using an approved method Fires can be connected to the supply using semi rigid pipe i e copper tube also independently certifi...

Page 5: ...on on the back of the appliance The top of the flue should also be capped off to prevent the entry of moisture etc consult building control if in any doubt 5 CLEARANCES TO COMBUSTIBLE MATERIALS AND SH...

Page 6: ...hrough walls seal the pipe ends to prevent debris entering the pipes 6 5 The fire must be mounted minimum 200mm from floor level 6 6 Hang the appliance on the wall and fix into position 6 7 Fully purg...

Page 7: ...on the gas access cover to the O position Undo the securing screw for the receiver holder on the right hand side of the appliance as shown below Pilot Burner Burner Outlet Battery Switch Battery Swit...

Page 8: ...gas access cover is in the O position fit four AA 1 5V batteries into the receiver unit Fit the PP3 9V battery into the transmitter hand set Press the battery switch located on the underside of the g...

Page 9: ...lit the igniter will stop another acoustic signal will confirm the pilot has been established if the pilot fails to establish repeat the process Due to the safe efficient nature of the fire it is not...

Page 10: ...tery isolator switch back to the I position Press here and slide down CAUTION With the exception of battery replacement the receiver must be located in the carrier at all times 9 6 Pairing Handset to...

Page 11: ...ine BEFORE you leave the installation If the appliance is not fitted in strict accordance with these instructions Burley cannot be held responsible for any damage caused and reserve the right to charg...

Page 12: ...laced the original manufacturer s parts must be used Controls The GAS CONTROL IS FACTORY SET AND NORMALLY NEEDS NO ADJUSTMENT Check for smooth operation of the gas valve Remove access cover check the...

Page 13: ...ings CHIP1000 900g CHIP1000 900g Glass GLA4530 GLA4530 USE ONLY GENUINE REPLACEMENT PARTS Parts ordered from our factory will normally take 5 7 working days to be delivered An Express service is avail...

Page 14: ...be carried out in accordance with BS5871 Pt 4 The catalytic converter needs heat to work therefore before you start testing the fire must have been lit and burning on full for at least 15 mins There a...

Page 15: ...e consult the relevant manufacturer Only use replacement catalyst supplied by Burley If you or the customer detects any odours from the fire please remember that the catalytic convertor is not an air...

Page 16: ...r a reasonable period of time so that the capacity of the meter is used On low Input appliances such as our flueless this is even more critical because uncertainties can creep in It is worth measuring...

Page 17: ...rmerly CORGI within the first year as with all gas products every gas appliances must be serviced every year The appliance has not been subject to misuse accident or repaired or fitted by anyone other...

Page 18: ...recycling WEEE Dispose of electrical equipment in an environmentally correct manner When disposing components containing Refractory Ceramic Fibres RCF we recommend that the items are not broken up bu...

Page 19: ...Page 19 of 20...

Page 20: ...iglo fires are protected by UK patents 2193802 2240620 and 2256920 Other Patents Pending Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Tel 01572 725570 Fax 01572 724390 www burley co uk...

Reviews: