38
Assembly
Type 8792, 8793 REV.2
→
Place Type 8792/8793 with assembly bridge on the rotary actuator and attach (see “Figure 17”).
Figure 17:
Swivel actuator attachment
If the X.TUNE ERROR 5 message is indicated after the
X.TUNE
function starts, the shaft of Type
8792/8793 is not correctly aligned with the shaft of the actuator
(see “Error message for P.Q.‘LIN; process controller Type 8793” on page
•
Check alignment (as described previously in this chapter).
•
Then repeat the
X.TUNE
function.
11.4
Remote operation with external position sensor
In the case of this variant, the positioner has no position sensor in the form of a rotary position sensor, but
an external position sensor.
Depending on the variant of Type 8792/8793, there are the following connection variants:
Device type
Interface
Position sensor
Setting in the menu
(ADD.FUNCTION)
Type 8792 Remote
digital (serial)
Remote sensor Type 8798
–
Type 8793 Remote
digital (serial)
Remote sensor Type 8798
POS.SENSOR
→
DIGITAL
For
menu description see chapter
analog (4...20 mA)
*
any high-resolution position
sensor
POS.SENSOR
→
ANALOG
For menu description see
chapter “16.1.21 POS.
Table 12:
Connection variants of external position sensor
* If the external position sensor is connected to the process controller Type 8793 via the analog
interface, it can be operated only as a positioner (position controller).
english
Summary of Contents for 8792