23
Settingthestationaddresses
7
SETTING THE STATION ADDRESSES
DIP switches 1 to 7 Bit 1 to Bit 7
The DIP switches are not read in until the device is switched on.
In the case of the PROFIBUS PA each station receives an address. These addresses are set with the DIP
switches 1 to 7.
The permitted address area is between 3 and 124.
Settings:
2
0
2
1
2
2
2
3
2
4
2
5
2
6
DIP -1
DIP -2
DIP -3
DIP -4
DIP -5
DIP -6
DIP -7
Address
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
3
:
:
124
125
126
* Delivery status: Address 126
If switch 8 is in the ON position, the internal address is used! This address can be set via the field bus.
7.1
LED display
The LED flashes if the device is using cyclic data transfer.
The LED lights up briefly when the device is connected.
If the device establishes an internal fault, the LED stays on constantly.
7.2
Watchdog
To improve fault detection, we recommend operating the device using cyclic data transfer with “
DP watchdog
”.
perm. address
range 3 ... 124
english
Type 8643 PA
Summary of Contents for 8643 PA
Page 47: ......
Page 48: ...www burkert com...