88
büS/CAN open-Design
15.4
büS/CANopen specification
15.4.1 General data
Baud rate:
configurable via DIP switches 7, 8 or via software (selectable values – see
chapter
“15.14.1 Setting the baud rate”)
factory setting: software configurable baud rate (
pre-selected: 500 kbit/s
)
Address:
1 ... 63 (via DIP switches 1 ... 6 adjustable);
factory settings: 0 = software configurable address / Node ID
(Node ID from 1 to 127 possible;
pre- selection: auto-addressing of the Node ID,
see chapter
“15.14.2 Setting the büS/CANopen address (Node ID)”)
Bus mode:
büS or CANopen (bus mode is software configurable only)
factory setting:
büS
Process data:
büS/CANopen or e. g. EtherNet/IP (depending on configuration)
Gateway /
SPS
6 byte
input
1 byte
output
Gateway /
EtherNet/IP
1 (...6) byte
input
1 byte
output
(Configurations for further bus systems on request)
Inputs:
6 byte with:
(Control head –> gateway) 4 byte position feedback in m (resolution: 1 mm)
(= feedback as cyclic position signal of the target),
1 byte NAMUR status feedback,
1 byte position feedback (3 discrete feedback signals from the position measuring
system (positions S1 to S3) + 1 discrete feedback signal from the external
initiator (S4);
power supply via büS/CANopen cable (11 ... 25 V DC)
(
The acyclic analogue position signal of the target can be read out e.g. as
parameter “8681_Current_Position_mm_DevXX” (resolution: 0.1 mm)
- see
chapter
“15.20 Access to parameters (Read / Write)” on page
Outputs:
1 byte for control of the 3 solenoid valves
(Gateway –> control head)
15.4.2
Total line length and drop line lengths of the bus cables
The bus line is a 4-core cable with additional shielding which must conform to the büS/CANopen specification.
The cable transmits both data/information and energy (low-voltage power supply for actuators and sensors)
The maximum total line length (sum of trunk lines and drop lines) of a network depends on the
baud rate.
Some baud rates and their corresponding maximum lengths are listed in the table below.
english
Control Head Type 8681