29
Technical Data
6.8.2
Service / maintenance notification (maintenance request)
Factory setting
for the "Service/maintenance notification" function:
not active.
When Service/maintenance notification is activated, this is indicated by a special flashing pattern - see
“21.2 Flashing pattern & fault signalling” on page
, for the büS/CANopen design, see the „Addi
-
tional Instructions for Type 8681 büS/CANopen“.
The Service/maintenance notification is used to observe predefined maintenance intervals which should
occur either after an adjustable number of switching cycles or when a certain time has elapsed. The PC
service program or the Bürkert Communicator is used – depending on the control head design – to adjust
the service/maintenance interval (number of days or switching cycles) as well as activation/deactivation of
the "Service/maintenance notification" function.
Connection to the PC is either via the service interface – see
– or communication takes place via
the Bürkert Communicator (only for büS/CANopen and IO-Link variants). Details about the “Service” menu
option are described in the software manual: “Software manual Type 8681 | PC service program” or can be
found in the Bürkert Communicator.
A feedback, indicating that a service / maintenance is required (Service/maintenance notification), occurs
when a Service/maintenance notification is activated after the following counter readings:
Counter readings
(service interval)
Factory setting
Adjustment range
Adjustment range
(IO-Link design only)
Switching cycle counter V1
10 000
(1 ... 255) x 1000
1 ... 4294967295
Switching cycle counter V2
50 000
(1 ... 255) x 1000
1 ... 4294967295
Switching cycle counter V3
50 000
(1 ... 255) x 1000
1 ... 4294967295
Operating duration
365 days
1 ... 65 535 days
The resettable operating hour and switching cycle counters are reset to "0" when a Device Reset occurs.
Service
on different
electronic modules:
for PC service-
program (e.g. at
24 V DC and AS-i),
for Bürkert Communi
-
cator (büS) at
IO-Link
design
Fig. 9:
Location of the Service interface on several electronic modules
6.8.3
Manual override function (magnetic)
Factory setting
for the magnetic manual override function:
active
.
For details compare also chapter
“22.1 Magnetic manual override” on page
151.
Deactivation
is possible using the PC service program (for IO-Link and büS/CANopen design via Bürkert
Communicator). Details are described in the software manual “PC service program” under the “SYSTEM/
Start-up” menu option (with the Bürkert Communicator, it is necessary to search for the corresponding
object).
The connection to the PC is via the Service interface – see
„Fig. 9“ (or for the IO-Link and büS/CANopen design
via büS stick to the Bürkert Communicator).