8625-2 Standard - 7
english
Operating voltage
24 V DC
Power consumption
max. 0.3 W (without proportional valve)
Output current (to valve)
max. 1.0 A
Operating temperature
- 10 °C ... + 60 °C / 14 °F ... 140 °F
Interference resistance
to EN50082-2
Interference emission
to EN50081-2
Inputs
Sensor input
PT100
temperatur range
- 50 °C ... 150 °C / - 58 °F ... 302 °F
resolution
0.25 °C or 0.45 °F
1)
precision
1.5 °C bzw 2.7 °F
1)
1 standard signal input
4 - 20 mA / 0 - 10 V, adjustable
resolution
10 Bit
input impedance (4 - 20 mA)
< 200
Ω
input impedance (0 - 10 V)
> 300 k
Ω
Output
PWM output
24 V - pulse width modulated
Controller
Control algorithm
PI control
Scan time T
A
50 ms
Amplification factor K
p
0,00 - 10,00 %/K
Reset time T
N
0,1 - 200,1 s
Scaling
-50 °C ... 150 °C or -58 °F ... 302 °F
Housing
Cable outlet
rotatable in 90° steps
System of protection
IP 65
Material
polyamide
Dimensions (WxHxD)
54 x 54 x 61 mm
Order no.
143 571
1)
Calibrated to 1 m conductor length and 0.5 mm² conductor cross-section.