33
Installationandwiring
Type 8025 /8035 Batch
Selector▶
C
▶makes▶it▶possible▶to▶configure▶the▶type▶of▶signal▶the▶
8025▶Batch,▶panel-▶or▶wall-mounted▶version,▶receives▶from▶the▶
remote▶flow▶sensor.
C
SENSOR TYPE
COIL
NPN/PNP
SENSOR TYPE
COIL
NPN/PNP
▶
→
Set▶the▶selector▶on▶the▶right▶
(default▶position)▶when▶the▶
signal▶from▶the▶flow▶sensor▶
which▶is▶connected▶to▶the▶
8025▶Batch▶is▶either:
•▶ a▶pulse▶signal,▶NPN▶or▶PNP
•▶ an▶"on/off"▶signal▶(Reed▶relay▶
for▶example)
•▶ a▶0-5▶V▶DC▶standard▶voltage▶
signal▶(TTL,▶for▶example)
▶
→
Set▶the▶selector▶on▶the▶left▶
when▶the▶signal▶from▶the▶
flow▶sensor▶which▶is▶con-
nected▶to▶the▶8025▶Batch▶
is▶a▶sine-wave▶signal▶(coil).
Fig. 28: Using selector "SENSOR TYPE" on a panel- or wall-
mounted version
When▶selector▶"SENSOR▶
TYPE"▶above▶is▶set▶on▶
"NPN/PNP",▶selector▶
A
▶▶
makes▶it▶possible▶to▶con-
figure▶the▶supply▶voltage▶for▶
the▶remote▶flow▶sensor.
SENSOR
SUPP
LY
+5V
L+
(L+)-12V
A
▶
→
If▶the▶device▶is▶energized▶with▶a▶
115/230▶V▶AC▶power▶supply,▶set▶
selector▶"SENSOR▶SUPPLY"▶on▶
"L+"▶(default▶position).
▶
→
If▶the▶device▶is▶energized▶with▶a▶
12-36▶V▶DC▶power▶supply,▶set▶
the▶voltage▶selector▶"SENSOR▶
SUPPLY"▶depending▶on▶the▶
voltage▶supply▶needed▶by▶the▶
remote▶flow▶sensor:▶"+5V",▶"L+"▶
or▶"(L+)-12V"▶(default▶position).
Fig. 29: Using selector "SENSOR SUPPLY" on a panel- or wall-
mounted version