28
Type 6520
4.4.2 Setting the Station Addresses
DIP switch 1 to 7
Bit 1 to Bit 7
In the Profibus-PA, each station is given an address, These addresses are set up
using the DIP switches 1 to 7.
The permissible address range lies between 3 and 124.
NOTE
The DIP switch is only read when the device is switched on.
4.4.1 Connections
DIP-switches for setting
station addresses
1
least significant bit (LSB)
8
most significant bit (MSB)
Connection PROFIBUS PA
with any polarity
23
- Sensor 2
21
+ Sensor 2
13
- Sensor 1
11
+ Sensor 1
Summary of Contents for 6520 NAMUR