![Burkert 3010 Operating Instructions Manual Download Page 10](http://html1.mh-extra.com/html/burkert-0/3010/3010_operating-instructions-manual_2832350010.webp)
8 - 3010
englisch
Standard signal input
0 - 10 V
0 - 20 mA
4 - 20 mA
left
right
+
1
2
3
1
2
3
1
2
3
1
2
3
-
L1
N
PE
NOTE
DIP switches for setting the standard signal input are located on the
circuit board.
S9 to S12 in Position 1: 10 V / 20 mA = OPEN
S9 to S12 in Position 2: 10 V / 20 mA = CLOSED
S13 and S14 in Position 1: 0 ... 10 V input
S13 and S14 in Position 2: 0/4 ... 20 mA input