17
Installation
Type 3281
7.7
LED display
The LED colours can be switched between standard and in line
with NAMUR NE 107, using the Bürkert Communicator software.
7.7.1
Display elements standard
LED
Status
Description
white
permanently on
Normal operation
yellow
permanently on
Valve not fully open
flashing
Out of specification
green
permanently on
Valve closed
red
flashing
Error
white, green or
red
flashing
Use to identify a device
in the büS network
orange
flashing
Function control: Work
is being carried out on
the device
no colour or LED
off
-
Valve without power
supply
7.7.2
Display elements NAMUR NE 107
LED
Colour
code
Status
Description
green
1
permanently
on
Diagnostics active
red
5
permanently
on
Failure, error or fault
green or
red
1 or 5
flashing
Use to identify a device
in the büS network
orange
4
permanently
on
Function check, work is
being carried out on the
device
yellow
3
permanently
on
Out of specification
no colour
or LED off
-
-
Valve without power
supply
english