Authorized cable plug e.g.
Type 2508 or other suitable
cable plug in accordance with
DIN EN 175301-803 Form A
Seal
max. 1 Nm
Note the voltage and current type as specified on the type
label.
Procedure:
→
Tighten cable plug (for permitted types see data sheet), observing
max. torque 1 Nm.
→
Check that seal is fitted correctly.
→
Connect protective conductor and check electrical continuity
between coil and body.
6.5.1 Electrical connection - Pulse
DC connections:
Terminal 1 =
Terminal 2 = open +
Terminal 3 = GND -
Protective conductor
connection
2
4
3
1
The connection terminals in the cable plug are identified with
the numbers 1 to 3 according to the terminals on the valve.
Procedure:
→
Connect the pulse valves (variable code CF 02).
→
For direct current versions connect negative terminal to terminal 3.
english