Plus-X IIU Installation Guide Rev B 

 

Network Settings 

Each Plus-X IIU must be assigned a static IP address for communication with the ARC Plus 
remote control system. However, using a dynamic IP address assigned by Dynamic Host 
Configuration Protocol (DHCP) is an easy way to do initial setup of the Plus-X IIU. This 
document describes the procedure for establishing initial communications with a Plus-X IIU in a 
network that supports DHCP and in a network that does not.  

The table below lists the firmware version in which DHCP functionality was introduced for the 
Plus-X IIU. The table also specifies the default hostname that must be used for initial connection 
to the Plus-X IIU when it is installed on a network that supports DHCP. 

Plus-X Unit 

DHCP Firmware Revision 

Hostname* 

Plus-X IIU 

1.1.3 

PLUSXIIU 

* Hostnames can be used in either upper or lower case. 

Initial Connection Using DHCP 

Connect the Plus-X IIU to your LAN and apply power. If this is the first power-up for a new unit 
or the first network connection after execution of a master-initialization, the Plus-X IIU will issue 
a DHCP request for an IP address. If the network supports DHCP functionality, a dynamic IP 
address will be assigned to the unit. To access the unit, launch a web browser and enter the 
h

ostname from the table above in the browser’s address field, followed by the forward-slash 

symbol as follows: PLUSXIIU/ 

The login screen shown below will be displayed. 

Select and confirm a password for the admin account and click the Save button.  

Note: If the page above is not displayed or the browser indicates that the page cannot be found, it is 
possible the connected network does not support DHCP. In this case follow the steps outlined in 

“Initial Connection Without DHCP”.  Otherwise, 

log in as shown below and 

continue to “Set a Static IP 

Address”.

 

Summary of Contents for Plus-X IIU

Page 1: ...Plus X IIU Installation and Operation Manual ...

Page 2: ...ings 5 Connecting the Plus X IIU to the ARC Plus 5 Connecting Analog and Status Inputs 6 Using Metering Inputs for Additional Status 7 Input Diagnostics 8 Restoring Factory Configuration 8 Uploading New Firmware 8 Getting Help 8 Warranty 9 Appendix A Specifications 10 Dimensions 10 Operating Temperature 10 Humidity 10 Power Requirements 10 Connectivity 10 Channel Capacity 10 Metering Input Range 1...

Page 3: ...onnected to each ARC Plus Front Panel Indicators Front panel of the Plus X IIU Indicator State Description Power LED Off Power is off Power LED Green Power is on Power LED Amber No firmware loaded contact Technical Support Power LED Red Resetting to factory default settings Link LED Green Connected to ARC Plus Link LED Red No connection to ARC Plus Rear Panel Features Rear panel of the Plus X IIU ...

Page 4: ...Hostnames can be used in either upper or lower case Initial Connection Using DHCP Connect the Plus X IIU to your LAN and apply power If this is the first power up for a new unit or the first network connection after execution of a master initialization the Plus X IIU will issue a DHCP request for an IP address If the network supports DHCP functionality a dynamic IP address will be assigned to the ...

Page 5: ...default static IP address of 192 168 0 100 To access the unit it will be necessary to connect your PC directly to the Plus X device using a crossover LAN cable or using a simple Ethernet switch In addition your PC s internal network interface must be set to a static IP address of the form 192 168 0 x In the Windows Control Panel search for Change Ethernet Settings then select Change adapter option...

Page 6: ...address field You will be prompted as shown in the previous section to provide a password for the admin account and then to log in to the admin account using the newly assigned password Set a Static IP Address The first screen displayed after initial login is the Settings page as shown below Enter a static IP address for this unit as assigned by your network administrator in the IP Address box and...

Page 7: ... previously assigned Additional fields must now be completed It may be necessary to obtain the Subnet Mask and Gateway IP address from your network administrator It is also necessary to assign the IP address of the ARC Plus unit that will be controlling the Plus X IIU It is also a good idea to change the hostname from the default value so conflicts will not occur if multiple Plus X devices of the ...

Page 8: ...tus or Command tabs as appropriate Locate an unused channel and click the button in the Source column This will bring up the Source dialog Click the Plus X channel button and choose the Plus X device and channel you wish to use 7 Configure labels limits and alarms for the newly added Plus X channels 8 Lastly you will need to calibrate the metering channels If you have not already connected the inp...

Page 9: ...Analog and Status inputs Once you have identified the connector blocks for your input channels attach wiring for each remote control channel to the connector block using the connector labels as a guide Secure the wiring using the built in set screws before attaching the connector block to the appropriate rear panel connector Using Metering Inputs for Additional Status Each of the 16 metering input...

Page 10: ...for diagnostic purposes and may be useful during initial setup or troubleshooting The values on this page are not updated in real time and should not be used for daily operation Restoring Factory Configuration To reset the unit to its default configuration press and hold the MASTER INIT button for three seconds The Power LED will turn red to confirm the configuration has been reset Note that resto...

Page 11: ...Technology A return authorization must be obtained before returning any equipment Materials returned under this warranty must be shipped freight prepaid and insured in the original shipping carton or suitable substitute to Burk Technology Inc 7 Beaver Brook Road Littleton MA 01460 Repairs not covered under this warranty will be made at prevailing shop rates established by Burk Technology THE WARRA...

Page 12: ... 63Hz 1A Power entry module with standard grounded power cord supplied 1A fuse protection Connectivity Ethernet connection to ARC Plus Channel Capacity 16 metering and 16 status inputs per unit Metering channels may be used as status inputs for a total of 32 status channels Metering Input Range 10 to 10VDC Metering Input Accuracy 99 75 accuracy full scale Status Input Range 0 to 28VDC or switch cl...

Reviews: