BULLDOG SpaceKeeper Vertical – Installation Operation Maintenance Manual 

14 

 
 

         

                              © Copyright 2013 CGC Group Inc       Installation Operation Maintenance Manual is Subject to Change without Notice- Last Revised Oct 1, 2014

 

 

up. If the switch does not close within the 5 minute ignore period, the compressor will 
immediately be turned off. Low pressure switch opens at 60 ± 3 psi and closes at 90 ± 3 
psi. 

e.

 

Air temperature sensor Ta – Sensor Ta will prevent compressor start-up if the air 
flowing through the unit is below 55

F. The sensor will also prevent the compressor 

startup or discontinue compressor operation if the air temperature is above 140

F and 

will reset at 135

F. A flash code of 4 will be initiated on the red diagnostic LED 15. 

f.

 

Water temperature sensor Tw – Sensor Tw will prevent compressor start-up and trip 
an alarm (a flash code of 3) if the outgoing fluid temperature is above 125

F and will 

reset the alarm at 120

F. The sensor will also trip at startup and during operation if the 

water temperature is below 55

F and will reset at 60

F. 

g.

 

Refrigerant temperature sensor Tr – Sensor Tr will prevent compressor start-up if the 
coil temperature is below 40

F and resets at 65ᵒF.  A flash code of 2 will be initiated on 

the red diagnostic LED 15. 
 
Any  of  the  above  faults  will  be  indicated  via  the  diagnostic  LED  and  the  appropriate 
diagnostic flash code. Please note the temperatures provided might vary by ±5

F.  

 

COOL OPERATION 

 

2.

 

Monitoring of the refrigerant cycle continues during operation of the compressor. The 
following malfunctions will cause the compressor to shutdown: 

a.

 

If the head pressure exceeds the set point of the high pressure switch, the switch will 
open and the control board will terminate the compressor operation within 10 
seconds. At this time a flash code of 6 will be initiated on the red diagnostic LED 15. 
Compressor operation will be restored in accordance with the “Intelligent Reset 
Algorithm” (see below). 

b.

 

If the suction pressure drops below the set point of the low pressure switch, the switch 
will open and if it remains open beyond the 5 minute ignore period after start up, 
compressor operation will be terminated within 10 seconds.  Compressor operation 
will be restored in accordance with the “Intelligent Reset Algorithm”. A flash code of 5 
on the red diagnostic LED will be initiated at this time. 

c.

 

Intelligent Reset Algorithm – If a low or high pressure switch opens and remains open 
for more than 10 minutes, a hard lockout will be initiated and the cooling mode will be 
locked off until the controls are manually reset. At the same time the fault relay K3 will 
be set to alarm; however, if the open switch closes within 10 minutes, a restart cycle is 
initiated. The restart cycle begins with a 10 minute delay after which if there is a cool 
call in place and all other enablers are within the start parameters, the compressor will 
again be put into operation. Should either of the pressure switches open again, the 
shutdown procedure will cycle again, followed by a restart. The intelligent reset will 
allow two open switch shutdowns and restarts in a 24 hour period and a third 

Summary of Contents for SKV008

Page 1: ...tion Operation Maintenance Manual is Subject to Change without Notice Last Modified November 2019 Installation Operation Maintenance BULLDOG SpaceKeeper Vertical Heat Pump SpaceKeeper Vertical Models...

Page 2: ...ions Clearance 2 INSTALLATION 5 GENERAL INSTALLATION CHECK 5 LOCATION 6 PLACEMENT 6 PIPING 6 Wiring 7 UNIT OPERATION 8 OPERATION Detailed 11 FAN OPERATION 13 HEATING OPERATION 13 COOL START UP 13 COOL...

Page 3: ...piping The unit should be stored in a non corrosive environment sheltered from conditions of extreme temperature or humidity Subjecting the unit to conditions of this nature may result in significantl...

Page 4: ...60 70 Unit Model 070 080 100 R410A Charge oz per circuit Single circuit Standard 80 90 100 Dual compressors 50 55 55 Weight Dimensions Clearance Weight Unit Dimensions Models 008 018 Models 020 036 Mo...

Page 5: ...c Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 1 2014 SIDE CLEARANCE in Front Compressor Fan section 36 Filter Left or Right 6 Rear 2 Opposite Filter...

Page 6: ...ation Maintenance Manual is Subject to Change without Notice Last Revised Oct 1 2014 Unit Clearance The Vertical product requires minimum clearances as indicated in the table below SIDE CLEARANCE in F...

Page 7: ...licable codes and regulations It is the responsibility of the installing contractor to ensure adequate service clearance for regular maintenance or for repair in place is exercised The installing cont...

Page 8: ...specified clearances to provide room for removal of all access panels see Table 1 for details 3 Provide access to water shut off valves and fittings Provide screwdriver access to the unit side panels...

Page 9: ...t Notice Last Revised Oct 1 2014 NOTE Insulation of the water piping loop is not required except where piping runs through unheated areas or areas on the exterior of the building The normal loop opera...

Page 10: ...ach heat pump unit with water that is at the proper temperature and flow rate Fan Operation Each heat pump has two speed fan operation The fan operates as follows LOW Speed First stage of heating mode...

Page 11: ...ration to become activated the suite temperature must rise above the cool set point temperature The thermostat will automatically stop cooling once the space temperature drops below the cool set point...

Page 12: ...to appropriate heat or cool mode based on seasonal conditions c Set heat or cool set point to your desired suite temperature ie 72 F or 22 C 4 When away for an extended period set the thermostat as fo...

Page 13: ...BULLDOG Heat Pump provides year round cooling and heating as controlled by the unit thermostat The BULLDOG Heat Pump provides cooling with a water cooled refrigeration circuit and provides heating usi...

Page 14: ...clude High Pressure Switch Low Pressure Switch Heat Call W on thermostat terminal Cool Call Y on thermostat terminal Fan Call G on thermostat terminal Auxiliary A on thermostat terminal Compressor shu...

Page 15: ...operate second compressor HEATING OPERATION 1 A call on W for heat will activate the fan at low speed It will also simultaneously energize the heat relay K2 and its associated LED The relay K2 will pr...

Page 16: ...t cycle continues during operation of the compressor The following malfunctions will cause the compressor to shutdown a If the head pressure exceeds the set point of the high pressure switch the switc...

Page 17: ...m of 5 minutes by the anti recycle timer A flash code of 3 will be initiated upon a high outgoing system fluid temperature shutdown f If the discharge air temperature drops below 40 F compressor opera...

Page 18: ...ower ON to each of the Heat W Cool Y Fan G or Aux A While most present day thermostats operate in this manner there are others that may or may not work properly The following should be checked out for...

Page 19: ...he unit is not powered if the board fuse is blown or if the electronics are damaged a fault condition will be indicated The fault relay is paralleled with the Fault LED which will be ON when no fault...

Page 20: ...h will extend the life of the hoses heat exchangers and other water side accessories Water Flow Rate Open all isolation valves to the unit Ensure that the entering and leaving fluid temperatures of th...

Page 21: ...h the electrical disconnect Ensure that the correct standby protocol is in place the following board lights will come on in standby Power HP LP and Alarm Inspect the fan section to ensure that it is c...

Page 22: ...ing power or on the individual compressor The monitor at incoming power will not allow the control voltage to reach the microprocessor unless phases are in correct rotation The Emerson Comfort Alert m...

Page 23: ...BULLDOG SpaceKeeper Vertical Installation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 1 20...

Page 24: ...LLDOG SpaceKeeper Vertical Installation Operation Maintenance Manual 22 Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 1 20...

Page 25: ...ee from dirt and debris Visual Inspection Visually inspect units and give special attention to hose assemblies Note any signs of deterioration or cracking and repair leaks immediately Amperage Check o...

Page 26: ...ical Installation Operation Maintenance Manual 24 Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 1 2014 MAINTENANCE STANDAR...

Page 27: ...G SpaceKeeper Vertical Installation Operation Maintenance Manual 25 Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 1 2014 T...

Page 28: ...G SpaceKeeper Vertical Installation Operation Maintenance Manual 26 Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 1 2014 T...

Page 29: ...G SpaceKeeper Vertical Installation Operation Maintenance Manual 27 Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 1 2014 T...

Reviews: