background image

DC50 Series Dual-Cool Climate Control 

Tube and DC70 Vest Instruction Sheet

Air Pressure

Breathing air pressure must be continually monitored at the point-of-
attachment while operating the respirator. A reliable air pressure gauge 
must be present to monitor the pressure during respirator operation.

Make certain that your breathing air compressor has sufficient 

capacity to deliver a minimum of 30 cfm per respirator wearer at 

all times. Because Dual-Cool has two cool tubes, it requires a higher 

than normal volume of air.

The Breathing Air Pressure Table in your respirator user manual defines 
the air pressure ranges necessary to provide the respirator with a volume 
of air that falls within the required range of 6-15 cubic feet per minute (cfm) 
or 170-425 liters per minute (lpm). (See 42 CFR, Part 84, Subpart J, 84.150) 

WARnIng

Failure to supply the minimum required pressure at the point-of-attachment 
for your hose length and type will reduce airflow and could result in death 
or serious injury.

Air Supply Hose

To maintain your Bullard respirator’s NIOSH approval, use only approved 
Bullard V10 Series hose(s) in lengths of 50 to 300 feet, or Bullard V5 Series 
hose in lengths of 25 to 50 feet. Bullard V11 hose-to-hose adapters MUST be 
used to connect V10 hose lengths together. Secure connection(s) until wrench 
tight and leak free.

WARnIng

WARnIng

The DC50 Dual-Cool climate control system is not recommended for cooling 
the air supply when the air temperature is less than 70° F. Because the DC50  
Dual-Cool may cool the incoming air by more than 30° F, it is possible for 
ice to form in the breathing tube and reduce the airflow. Failure to observe 
these warnings could result in death or serious injury.

Compressed air must be dry enough to prevent ice buildup in the cold airstream. 
Ice could reduce airflow into the respirator hood.

Ordering Information

CATAlOg 

nuMBeR DeSCRIPTIOn

DC5040 

 1

4

” Industrial Interchange (Hansen compatible) quick-

disconnect nipple, adjustable temperature control, CH60 
connector hose, heat shield and belt

DC70Ml

 

 Medium/Large Cooling Vest

DC70XlXXl

 

 X-Large/XX-Large Cooling Vest

DC705X

 

 5X-Large Cooling Vest

CH60

 

 Connector  Hose

4612

 

 Nylon  Belt

HSDC

 

 Heat  Shield

Use of any other air supply hose voids NIOSH approval of the entire 
respirator assembly and could reduce the airflow to the respirator, 
possibly resulting in death or serious injury to the respirator wearer. 
Failure to observe these warnings could result in death or serious 
injury.

www.bullard.com

Summary of Contents for DC50 Series

Page 1: ...ments for Grade D breathable air include Oxygen 19 5 23 5 Hydrocarbons in mg m3 of gas 5 mg m3 max Carbon monoxide 10 ppm max Carbon dioxide 1 000 ppm max Odor No pronounced odor No toxic contaminants at levels that make air unsafe to breathe Specific measurement of odor in gaseous air is impractical Air normally may have a slight odor The presence of a pronounced odor should render the air unsati...

Page 2: ...r Bullard V5 Series hose in lengths of 25 to 50 feet Bullard V11 hose to hose adapters MUST be used to connect V10 hose lengths together Secure connection s until wrench tight and leak free Warning Warning The DC50 Dual Cool climate control system is not recommended for cooling the air supply when the air temperature is less than 70 F Because the DC50 Dual Cool may cool the incoming air by more th...

Page 3: ...Cool assembly is on your right hand side 3 Don the vest Use the Velcro closure strips to adjust loosely for size NOTE The vest should mount over the belt with the Dual Cool unit positioned in the V of the vest found on the right hand side Figure 1 4 Snap the quick disconnect nipple found on the end of the cooling vest connector hose into the quick disconnect coupler on the Dual Cool Figure 3 5 Don...

Page 4: ...s maximum airflow out of the Dual Cool tube s exhaust ports To obtain air that is closer to ambient temperature turn air temperature control knobs clockwise If knobs are closed completely your respirator will receive air that is essentially at ambient temperature NOTE There are separate controls to adjust the temperature of the air that is distributed to the vest and the breathing zone The right h...

Reviews: